Section 9
Establishing connection and verifying the IEEE C37.118/1344 communication
68
IEC140000134 V1 EN
1.1. Navigate to the Settings tab.
1.2. Force the IP stack to IPv4 by setting the parameter ForceIPv4 to True.
2.
Set the Connection Parameters on PMU Connection Tester for TCP communication
according to the PMU configuration.
IEC140000135 V1 EN
1MRK 511 366-UUS -
IEC140000134-1-en.vsd
IEC140000135-1-en.vsd
Commissioning manual