1MRK 511 366-UUS -
Establishing connection and verifying the IEC 61850 communication
Section 8
8.1
8.2
Commissioning manual
Establishing connection and verifying the
IEC 61850 communication

Overview

The rear OEM ports are used for:
process bus (IEC 61850-9-2LE) communication
IEEE C37.118/1344 communication
substation bus (IEC 61850-8-1) communication.
For IEC 61850-8-1 redundant communication, both rear OEM ports are utilized. In this
case IEC 61850-9-2LE communication can not be used.
IEC 61850-9-2LE process bus communication is not supported in the
IED.

Setting the station communication

To enable IEC 61850 communication the corresponding OEM ports must be activated.
The rear OEM port AB and CD is used for IEC 61850-8-1 communication. The rear OEM
port CD is used for IEC 61850-9-2LE communication. For IEC 61850-8-1 redundant
communication, both OEM port AB and CD are used exclusively.
IEC 61850-9-2LE communication can only be used on OEM rear port
X311:C, D.
To enable IEC 61850 station communication:
1.
Enable IEC 61850-8-1 (substation bus) communication for port AB.
1.1. Set values for the rear ports AB.
Section 8
63