Warning lights
BOILER STATUS
Power-on
Vent cycle
OFF status
No heat request (stby)
Transitional ignition/
overtemperature
Presence of flame
Chimney sweep
Screed heater
14.1 Reset function
In order to reset the boiler's operation in the event of a fault, it is necessary
to access the fault description screen. If the lockout is of a non-volatile type
that requires a reset procedure, this will be indicated on the screen, and can
be carried out by pressing the "ok" button on the REC10.
LIMIT THERMOSTAT
PRESS OK RESET
At this point, if the correct operating conditions have been restored, the
boiler will restart automatically.
If the attempts to reset the fault do not restore the boiler's functionality,
please contact your local Customer Support Service.
Up to a maximum of 5 reset attempts can be made using the REC10, after
which the machine must be disconnected from the power supply to reset
the number of attempts available.
b
Request the intervention of the Technical Assistance Centre.
LIMIT THERMOSTAT
REC10 ATTEMPTS EXHAUSTED
RED LED
GREEN LED
flashing
flashing
0.5 sec. on/1 sec. off
0.5 sec. on/1 sec. off
flashing
0.3 sec. on/0.5 sec. off
flashing
0.3 sec. on/0.5 sec. off
flashing
0.3 sec. on/0.5 sec. off
ON
ON
flashing
flashing
1 sec.on/1 sec. off
1 sec.on/1 sec. off
E020
E020
RED and GREEN
NOTES
flashing
The red and green LEDs come on at the same time
0.5 sec. on/0.5 sec. off
The red and green LEDs come sequentially one at a time
Only if the flame is present
The red and green LEDs come on alternately