5.2.2
Configuration of the zone
It is possible to customise the management of the heating zone by
accessing the ZONES MANAGER menu.
- Access the technical parameters as explained in the section "4.1 Access
to the technical parameters" .
- In sequence select INSTALLATION, ZONES MANAGER and MODIFY
ZONE with the "up" and "down" keys, confirming the selection.
INSTALLATION
PARAMETERS
THERMOREGULATION
RANGE RATED
CALIBRATION
INSTALLER
ZONES MANAGER
SENSOR CALIBRATION
SYSTEM RESET
INSTALLER
MODIFY ZONE
DELETE ZONE
INSTALLER
- Select the desired heating zone and then choose from among the options
with the "up" and "down" keys, confirming the selection:
INSTALLER
- TYPE OF ACTUATION
Set the parameter in question to ITRF05/AKM (default value)
- TYPE OF HEAT REQUEST
This parameter allows you to specify the type of heat request, it is
possible to choose from among the following options:
THERMOSTAT (factory setting): the heat request is generated with an
ON/OFF thermostat
REC10 MASTER: the heat request is generated by the REC10
MASTER; in this case the REC10 assumes the function of MACHINE
INTERFACE
TECHNICAL
INSTALL
INSTALL
ADD ZONE
INSTALL
MAIN
- TYPE OF ZONE
This parameter allows you to specify the type of zone to be heated, it
is possible to choose from among the following options:
HIGH TEMPERATURE (factory setting):
LOW TEMPERATURE
- MIN SET HEAT
This parameter allows you to specify the minimum heating setpoint that
is possible (range 20°C - 80.5°C, default 40°C for high temperature
systems - range 20°C - 45°C, default 20°C for low temperature
systems)
- MAX SET HEAT
This parameter allows you to specify the maximum heating setpoint that
is possible (range 20°C - 80.5°C, default 80.5°C for high temperature
systems - range 20°C - 45°C, default 45°C for low temperature
systems)
- CHANGING NAME
This parameter allows you to attribute a specific name to the heating
zone
- POR
This parameter allows you to enable the central heating programming
timing for the zone concerned if the heat request is carried out using a
room thermostat
Time schedule not enabled = 0
When the room thermostat contact closes the heat request is always
met without any time band limitation
Time schedule enabled = 1
When the room thermostat contact closes the heat request is enabled
according to the programming timing.
Note: in this case make sure that the operating mode of the zone is set
to AUTO in the STATE menu.
5.2.3
Anti-legionella function (only if connected a storage
tank with probe)
The machine has an automatic ANTI-LEGIONELLA function that, if
necessary, heats the domestic water to 65°C and keeps it at that temperature
for 30 minutes to prevent the proliferation of bacteria in the storage tank.
This function can be set to be activated every day or every week.
This function is not performed if the storage tank temperature has reached
65°C over the past 24 h - in case it is set to start daily - or over the last 7
days - in case it is set to start once a week.
If the function is activated, it is performed every day at 3:00 a.m. if set to
start every day, or on Wednesdays at 3:00 a.m. if set to start every week.
Once the function is in progress, it has top priority and cannot be interrupted.
b
The function is not performed when the boiler is OFF.
The function can be activated by accessing the TECHNICAL menu of
REC10:
- select MENU from REC main page and press CONFIRM
- access the technical parameters as explained in the section "4.1 Access
to the technical parameters"
- select ANTI-LEGIONELLA using with the "up" and "down" keys,
confirming the selection
THERMOREGULATION
RANGE RATED
CALIBRATION
ANTI-LEGIONELLA
INSTALLER
- select one of the options FUNCTION NOT ACTIVE, DAILY FUNCTION,
WEEKLY FUNCTION with the "up" and "down" keys, confirming the
selection
TECHNICAL
SWEEPER
ENGLISH
15