Boiler Type - Beretta EXCLUSIVE R Installer And User Manual

Hide thumbs Also See for EXCLUSIVE R:
Table of Contents

Advertisement

EXCLUSIVE
Whenever a "NEW" configuration is selected, proceed as follows:
- select REC10 functionality:
ON BOARD: if the REC10 is used only as a system interface and not as
an ambient regulator
AMBIENT: if the REC10 is used as a system interface and also as an
ambient regulator of the zone where it is installed
THE REC10 INSTALLED?
- select the type of boiler choosing between:
- CH ONLY: when the boiler doesn't manage domestic hot water (case A)
- STORAGE TANK: when the boiler manages a hot storage tank. NOTE:
in this case you will be asked to specify the type of hot water request
(THERMOSTAT - case B; or PROBE TEMPERATURE - case C)
If selected a storage tank with probe, is required if there is also to
manage a solar system: answer NO to this question
INSTANTANEOUS
STORAGE TANK
SELECT THE PLANT
- Once the guided procedure has finished, the REC10 will go to the initial
screen.
Then proceed with the reprogramming of the boiler, carrying out the
operations described in the section "5.2 Programming the boiler" .
5.22 Replacing the REC10 MASTER
b
The system's configuration operations need to be carried out by
professionally qualified personnel of the Technical Assistance Centre.
When replacing the REC10 MASTER, at the subsequent restart it displays
an initial screen with the firmware revision.
Pressing "ok" starts a guided procedure for configuring the system, see
section "5.20 System configuration" . Follow the procedure and carry out the
FROM AKM type of configuration.
MULTI ZONE CONTROLLER
REC10 V01.26
PRESS ANY KEY
TO CONTINUE
26
BOILER
WHERE IS
ON BOARD
AMBIENT
PLANT
CH ONLY
CONFIGURATION
OF CONFIGURATION
5.23 Replacing the AKM01 board
The configuration operations should be carried out by professionally
qualified personnel of the Technical Assistance Centre.
The systems continually carries out a consistency control between the
saved configuration data on the AKM01 electronic board and those saved
in the REC10; therefore, when replacing the AKM01 electronic board, it can
happen that the system detects an inconsistency between the data saved
on the AKM01 and that in the REC10.
In this case, the latter will ask the user which of the two configurations is
to be considered valid; selecting to recuperate the configuration from the
REC10 itself it is possible to avoid reconfiguring the machine:
- select REC10 with the "up" and "down" keys, confirming the selection.
SELECT THE TYPE
OF CONFIGURATION
5.24 Parameters combustion check
Although the parameters referring to the new combustion control
system ACC (Activate Combustion Control) are preset in the factory, the
simultaneous replacement of both electronics boards (AKM and REC 10
MASTER) could make necessary to re-programming these parameters.
- Access the technical parameters as explained in the section "4.1 Access
to the technical parameters" setting the password SERVICE
- Select COMBUSTION MONITORING with the "up" and "down" keys,
confirming the selection
EXHAUST PROBE RESET
ALARM HISTORY
COMBUSTION MONITORING
SERVICE
- Select GAS TYPE
- Set this parameter depending on the type of gas of the boiler. The values
for this parameter are NG = NATURAL GAS - LPG = LPG
COMBUSTION MONITORING

BOILER TYPE

COMBUSTION OFFSET
SERVICE
SELECT THE TYPE
FROM AKM
NEW
FROM AKM
REC10
TECHNICAL
PARAMETERS
VENT CYCLE
GAS TYPE