Six–Conductor Connection To The Line Supply - Siemens SIMODRIVE 611 digital Configuration Manual

Drive converters
Hide thumbs Also See for SIMODRIVE 611 digital:
Table of Contents

Advertisement

Aotewell Ltd
05.01
05.08
8.15.2
Schematic diagram
F
(T10 A)
N
2L1
2L2
2L3
F
(X A)
N
1L1
1L2
1L3
PE
Note:
1) L
for 5 kW and 10 kW integrated, therefore not necessary here!
k
2) DC link connection not permissible for six–conductor connection to the line supply!
Fig. 8-35
© Siemens AG 2008 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 05/2008 Edition
HongKong|UK|China
www.aotewell.com
Six–conductor connection to the line supply
Note
S
All X181 connections of a drive group must be electrically switched in
parallel!
S
All of the jumpers at X181 must be removed!
S
A maximum of four monitoring modules may be connected at X181 of an
NE module.
S
If a DC link is buffered (DC link connection), the voltage must always be
taken from between the reactor (L
S
Different line supplies may be used, e.g. using UPS.
S
For all of the following examples, cables must be routed so that they are
short–circuit and ground–fault proof (or fuse)!
NE
Filter (5 kW)
X181
M500
P500
2U1
1U1
2V1
1V1
2W1
2)
1W1
P600
M600
Filter (X kW)
1)
U1
V1 W1
L
K
Examples for correct six–conductor connection to the line supply with a maximum of four monitoring modules
connected to a line infeed module (NE module)
sales@aotewell.com
8.15 Examples of correctly and incorrectly connecting NE
) and the line supply infeed (NE).
K
Correct!
e.g. NCU PMxx
Twisted
cable
PE
Six–conductor connection
to the line supply
Industry Automation
8 Important Circuit Information
v4 MM
PMxx
MM
PMxx
X181
M500
P500
2U1
1U1
2V1
1V1
2W1
1W1