6 Infeed Modules
6.2 Function overview and settings
Switch S1.5
Switch S1.6
6-156
www.aotewell.com
This function is only applicable in conjunction with I/R modules
Order No.: 6SN114V–1BV0V–0VA1
OFF: regulated infeed active (default setting)
ON:
Unregulated operation in the infeed direction V
Notice:
For unregulated operation of the I/R units with V
must be reduced (derated) as specified in Section 4.5.
OFF: Squarewave current operation (current with a squarewave shape is
drawn from the line supply)
ON:
This function is only applicable in conjunction with I/R modules with
Order No.: 6SN114V–1BV0V–0VA1
sinusoidal current operation (sinusoidal current is taken from the line supply)
Note
The total length of the power cables (motor supply cables and DC link cables)
may not exceed 350 m for sinusoidal current operation and 500 m for
squarewave current operation.
SIMODRIVE 611 Configuration Manual (PJU) – 05/2008 Edition
sales@aotewell.com
Industry Automation
= V
 1.35
DC link
line
= 400 V/415 V, the power
line
© Siemens AG 2008 All Rights Reserved