External Cooling - Siemens SIMODRIVE 611 digital Configuration Manual

Drive converters
Hide thumbs Also See for SIMODRIVE 611 digital:
Table of Contents

Advertisement

2 System Configuration
2.7 Infeed modules
2.7.3

External cooling

M5 screw
Tightening torque 3 Nm
Discharged air,
electronics
Closed- -loop
control
Power module with
external cooling
and heatsink seal
Air intake for
the electronics
T ≤ 40
Fig. 2-9
Power module with inserted control unit, external cooling
2-60
www.aotewell.com
Rear cabinet panel
(bare metal)
Discharged air,
heatsink
Fan assembly
Air intake for
the heatsink
0
T ≤ 40
C
0
C
Note
Refer to Fig. 2-9 for the air flow direction and the dimension drawing in
Chapter 12 for the ventilation space. The dimensions of the installation frame
are presented in the dimension drawing in Chapter 12.
Notice
For external heatsinks and fans, a high degree of pollution restricts the module
cooling. This can cause the temperature monitoring function in the power
module to respond. The heatsinks and fans must be checked for accumulated
dirt at regular intervals.
Clean when required!
SIMODRIVE 611 Configuration Manual (PJU) - - 05/2008 Edition
sales@aotewell.com
First mount the frame and
then seal!
Seal the mounting frames
with respect to one another
and to the rear cabinet panel
(e.g. using Terostat- -91
made by Henkel).
The sealant (preferably
inside the cabinet) should be
applied around the
circumference so that
degree of protection IP54 is
ensured.
It should be checked that the
foam rubber seal is tight - - if
required, seal!
Mounting
frame
© Siemens AG 2008 All Rights Reserved
Industry Automation
05.08
05.01
+86-755-8660-6182