9.1.2
General
information
Cooling clearance
Fig. 9-4
© Siemens AG 2008 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 05/2008 Edition
HongKong|UK|China
www.aotewell.com

Mounting conditions, internal cooling

Note
The regulations described in the "SINAMICS S120 Booksize / SIMODRIVE
System Manual" switchgear cabinet integration system manual
Order No.: 6SL3097–0AT00–0APV must be observed for the heat dissipation!
If the guidelines for installing/mounting SIMODRIVE 611 equipment in the cabi-
net are not carefully observed, this can significantly reduce the service life of the
equipment and result in premature component failure.
The following specifications must be carefully observed when mounting/instal-
ling a SIMODRIVE 611 drive group:
S
Cooling clearance
S
Cable routing
S
Air flow, climate–control equipment
Minimum 100 mm clearance at the top and bottom for cooling.
Incorrect
80 mm
Ä Ä Ä
40 mm
Ä Ä Ä
SIMODRIVE 611
40 mm
Ä Ä Ä
Ä Ä Ä
Cooling clearance
Air intake temperature, max 40 °C, at higher temperatures (max 55 °C), the
power must be reduced (derating).
sales@aotewell.com
9.1 Installation and connecting–up regulations
Correct
100 mm
SIMODRIVE 611
Channel cable
100 mm
Industry Automation
9 Cabinet Design and EMC
Ä Ä Ä
Ä Ä Ä
Cooling clearance
top and bottom
100 mm
Ä Ä Ä
Ä Ä Ä
9-335