Connection Conditions For Line Supply Infeed Modules - Siemens SIMODRIVE 611 digital Configuration Manual

Drive converters
Hide thumbs Also See for SIMODRIVE 611 digital:
Table of Contents

Advertisement

Aotewell Ltd
05.01
11.05
05.08
6.3.1
Supply voltage
and
frequency
Table 6-5
Supply voltage: U1, V1, W1
With derating to 70% P
Frequency
1) If the derating performance does not suffice, the next larger line supply infeed module should be used.
Table 6-6
Module
The NE modules are designed for symmetrical 3–phase line supplies with grounded neutral point: TN systems. No further
consumers with asymmetric load (single–phase) may be connected for transformers with non–loadable neutral point.
The line supply specifications according to EN 50178 are complied with as a result of the series (upstream) line reactor (for
5 kW and 10 kW UI, these are integrated in the module).
Notice
The described minimum line supply fault level is needed to trigger the fuses in the case of ground fault and short–circuit within
the prescribed time in order to protect the plant and prevent damage and faults at other devices.
An insufficient system fault level (short–circuit power) increases the triggering and also prevents the triggering of the fuses.
This can cause, for example, arcs with the consequent fire of danger.
The required apparent power of the line supply for each NE module is S
a matching transformer, the minimum S
UI modules
I/R module
No ground faults
© Siemens AG 2008 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 05/2008 Edition
HongKong|UK|China
www.aotewell.com

Connection conditions for line supply infeed modules

The line supply infeed modules are adapted to the actual line supply conditions
using switches S1.1 and S1.4 (refer to Chapter 6.2).
The converter system is designed for operation connected to grounded TNS
and TNC line supplies (VDE 0100 Part 300). For other line supply types, an
upstream transformer must be used with isolated windings in a YN vector group
on the secondary side (refer to Chapter 7 when dimensioning/selecting this
transformer).
Supply voltage and frequency
NE modules
1)
and P
Minimum 323 ... .360 V 3 AC
n
max.
Line supply connection conditions for NE modules
of 0.73 times the value from the table is permitted.
K
Operation on line supplies from S
Pn I/R module
Sinusoidal current operation (S1.6
16 kW
36 kW
55 kW
80 kW
120 kW
Note
UL requirement, maximum permitted line supply short–circuit current SCCR v
65 kA.
Before powering–up the system for the first time, the cabinet wiring, the motor/
encoder feeder cables and DC link connections must be carefully checked to
ensure that there are no ground faults.
sales@aotewell.com
S1.1, S1.4 = OFF
Vn = 3–ph. 400 V AC
3–ph. 360..440 V AC
3–ph. 373..457 V AC 3–ph. 432..509 V AC
45...65 Hz
Description
= P
n
n
/Pn w 30
Kline
= ON)
S
line w 1.0 MVA
K
(70 S Pn
)
I/R module in kW
S
line w 2.5 MVA
K
(70 S Pn
)
I/R module in kW
S
line w 4.0 MVA
K
(70 S Pn
)
I/R module in kW
S
line w 5.0 MVA
K
(60 S Pn
)
I/R module in kW
S
line w 7.0 MVA
K
(60 S Pn
)
I/R module in kW
Industry Automation
6 Infeed Modules
6.3 Technical data
S1.1 = ON
S1.4 = ON
Vn = 3–ph.
Vn = 3–ph.
415 V AC
480 V AC
55...65 Hz
S 1.27. If an infeed is operated by itself on
Squarewave current operation
(S1.6 = OFF)
S
line w 1.5 MVA
K
(100 S Pn
I/R module in kW
S
line w 3.5 MVA
K
(100 S Pn
I/R module in kW
S
line w 5.5 MVA
K
(100 S Pn
I/R module in kW
S
line w 6.5 MVA
K
(80 S Pn
I/R module in kW
S
line w 9.5 MVA
K
(80 S Pn
I/R module in kW