Advertisement

5.
Confirm proper option wiring.
Depending on the drive model, some drives may require routing the wiring to the
outside as shown in
Route the wiring inside the enclosure through the lower wiring cover to the outside
as shown in
outside.
Figure 15
Figure 15 Wire Routing Examples
6.
Select the proper PROFIBUS-DP dedicated communication cable according to
Table 6
and
Firmly connect the PROFIBUS-DP communication cable to option communication
connector CN4.
Install PROFIBUS-DP communications cables apart from main-circuit wiring and
other electrical and power lines. Ensure the cable end is firmly connected (see
Figure
18). Refer to
details.
Note: Maximum transmission distance is 100 m (328 ft.). Minimum wiring distance between stations
is 0.2 m (7.9 in).
7.
After connecting the prepared cable for the 9-pin D-sub communication connector
CN5, recheck the option wire routing performed in step 6..
YASKAWA ELECTRIC TOBP C730600 82B YASKAWA AC Drive Option SI-P3 Installation Manual
Figure
15.
Figure 16
for the drives that do not require routing the wiring to the
Table
7.
Communication Cable Specifications on page 30
5 Installation Procedure
Figure 16
Figure 16 Wire Routing Examples
Wiring cover
for
27