Maintenance; Power Supply Board Stand-By Battery Specifications; Power Supply Board Led Diagnostics; Access Power Controller Led Diagnostics - Altronix eFlowNAD8V Series Installation Manual

Access power controllers with power supply/chargers
Table of Contents

Advertisement

15. Multiple power supply inputs (Fig. 2, pg. 8):
When using an additional Listed external power supply, jumpers J1 and J2 located on corresponding
ACM8CB board must be cut (Fig. 2c, 2d, pg. 8 and Fig. 5, pg. 11). Connect external Listed power-limited
access control power supply to the terminals marked [– Control +] (These terminals are paralleled to the
[– Power +] terminals). When using DC power supplies, polarity must be observed. When using AC power
supplies, polarity needs not be observed (Fig. 2d, pg. 8). All field wiring connections must be made
employing suitable gauge CM or FPL jacketed wire (or equivalent substitute) (Fig. 4a, pg. 10).
Unit should be tested at least once a year for the proper operation as follows:
FACP Supervision: To ensure proper connection and operation of the Fire Alarm disconnect hookup please
Normally Open Input:
Normally Closed Input:
FACP Signal Circuit Input: It is necessary to trigger the Fire Alarm System. In all of the above scenarios
Note: All outputs [OUT 1 - OUT 8] must be in a normal (de-energized) condition prior to testing. When the
unit is configured for Normally Open (Fig. 8, pg. 10) or Normally Closed (Fig. 10, pg. 10) latching operation,
it is necessary to reset the Fire Alarm Disconnect by activating the Normally Closed reset switch.
Output Voltage Test:
Battery Test:
Note: Maximum charge current is 1.54A.
Expected battery life is 5 years; however, it is recommended to change batteries within 4 years or less if necessary.

Power Supply Board Stand-by Battery Specifications:

Battery
eFlow4NA8DV
7AH
30 Mins./4A
12AH
35 Mins./4A
40AH
Over 4 Hours/4A
65AH
Over 4 Hours/4A
Red (DC)
ON
ON
OFF
OFF

Access Power Controller LED Diagnostics:

LED
LED 1- LED 8 (Red)
Trg (Green)
- 6 -
follow the appropriate procedure below:
Placing a short between terminals marked [T] and [+ INP] will trigger the Fire
Alarm Disconnect. Remove the short to reset.
Removing the wire from terminal marked [INP –] will trigger the Fire Alarm
Disconnect. Replace the wire to terminal marked [INP –] to reset.
the green TRG LED of the ACM8CB will illuminate. All outputs selected for Fire
Alarm Disconnect will activate releasing locking devices.
Under normal load conditions the DC output voltage should be checked for proper
voltage level (refer to eFlowNA8DV series Configuration Chart, pg. 3).
Under normal load conditions check that the battery is fully charged, check specified
voltage at the battery terminals and at the board terminals marked [– BAT +] to
ensure that there is no break in the battery connection wires.
eFlow6NA8DV
10 Mins./6A
30 Mins./6A
Over 4 Hours/6A
Over 4 Hours/6A

Power Supply Board LED Diagnostics:

Green (AC/AC1)
ON
OFF
ON
OFF
ON
Output relay(s) energized.
FACP input triggered (alarm condition).

Maintenance:

eFlow102NA8DV
Over 2 Hours/10A
Over 4 Hours/10A
Power Supply Status
Normal operating condition.
Loss of AC. Stand-by battery supplying power.
No DC output.
Loss of AC. Discharged or no stand-by battery. No DC output.
5 Mins./10A
30 Mins./10A
OFF
Output relay(s) de-energized.
FACP normal (non-alarm condition).
eFlowNA8DV Series Installation Guide
eFlow104NA8DV
5 Mins./10A
30 Mins./10A*
Over 2 Hours/10A
Over 4 Hours/10A