Specifications; Electrical; Operational Environment; Hardware - Honeywell Unitary Installation Instructions Manual

Controller-230 vac
Table of Contents

Advertisement

HONEYWELL UNITARY CONTROLLER - 230 VAC - INSTALLATION INSTRUCTIONS

SPECIFICATIONS

Electrical

Table 3 Electrical Specification
Parameter
Rated input voltage
Maximum Nominal
Power Consumption
(for IP, MS/TP, and T1L
models)
Full Load Power
Consumption
(Maximum load
including external
loads, Sylk™, Bluetooth,
Communication,
Universal IO output,
24 VDC output, and load
on the DO CHPs) for IP,
MS/TP, and T1L.
Frequency Range
Auxiliary Output
Type of loads
Impulse Voltage
Material Group
Period of electric stress
across insulating parts
Classes of control
function
Type of Output
Waveform

Operational Environment

Table 4 Operational Environment
Parameter
Storage
-40 °F to 150 °F (-40 °C to 66 °C)
Temperature
-40 °F to 149 °F (-40 °C to 65 °C)
with 0.6 A cumulated across all
Operation
chopper outputs.
Temperature
-40 °F to 122 °F (-40 °C to 50 °C)
with 1.5 A cumulated across all
chopper outputs.
Humidity
5 % to 95 % RH, non-condensing
31-00610-01
Specification
230 VAC ± 10 %
Small:
IP and T1L: 45 VA
MS/TP : 60 VA
Large:
IP and T1L: 60 VA
MS/TP: 75 VA
Small:
IP: 170 VA
MS/TP, and T1L: 200 VA
Large:
IP: 200 VA
MS/TP and T1L: 210 VA
50/60 Hz
24 VDC at 75 mA (shared
between terminals 38, 48,
65 and 72)
Resistive or inductive loads
4000 V (4 kV)
IIIb
Long
Class A control
Rectangle
Specification
Table 4 Operational Environment
Protection
IP20, NEMA 1
Pollution
2
degree
Additional
tests
Ball Pressure and Glow wire test
conducted

Hardware

Table 5 Hardware Specification
Parameter
Crossover processor i.MXRT ARM
CPU
CORTEX-M7
Memory
16 MB QSPI Flash, 16 MB SDRAM
Capacity
BACnet™ IP (RJ45): 2 x RJ-45
Ethernet ports with a protection that
allows loop topology to continue the
Ethernet
communication with other
controllers even if one node fails,
when used with an RSTP supporting
device.
24 hours backup after power failure.
Real Time
After 24 hours, the time will reset to
Clock
factory default time until the user
performs a BACnet™ Time Sync
Transmission or reception of
Small LED
communication signal (green)
Controller status (Green, Yellow, and
Large LED
Red)

Communications

Table 6 Communication Specification
Parameter
Protocol supported
IP Addressing
Modes
Sylk™ bus
*Auto Baud rate detection is provided for the
BACnet™ MS/TP controllers.
6
Specification
Specification
• BACnet™ IP (RJ45 or T1L)
• BACnet™ MS/TP*
• Modbus RTU (Modbus
client)
• Bluetooth (Optional)
• Dynamic: DHCP and Link
Local
• Static: Assigned
2-wire, polarity-insensitive