Table 2-60 Range/Limit Tab Configuration Parameters - Honeywell UMC800 Reference Manual

Control builder function block
Hide thumbs Also See for UMC800:
Table of Contents

Advertisement

2.74 TPSC (3POS) Function Block,
Configuration Parameters, continued
RANGE/LIMIT TAB, continued
Properties Group
Parameter
Ranging
Display
`
Range (EU)
Limiting
SP Rate Up
3/99

Table 2-60 Range/Limit Tab Configuration Parameters

Index#
3
PV High
range
PV Low
4
Range
N/A
Decimal
Places
N/A
Units
DEV Bar
N/A
10
SP High
Limit
11
SP Low
Limit
25
Out High
Limit
26
Out Low
limit
SP Rate
34
Down
35
Function Block Reference Guide
continued
Parameter Description
PV High Range Value
PV Low Range Value
Number of digits after decimal
point for display
Engineering units for display
Deviation Bar Range on the
Operator Interface
Setpoint High Limit Value -
prevents the local and remote
setpoints from going above the
value set here.
Setpoint Low Limit Value -
prevents the local and remote
setpoints from going below the
value set here.
Autotuning Output High Limit
Value - is the highest value of
the output beyond which the
motor no longer affects the
process.
Autotuning Output Low Limit
Value - is the lowest value of the
output beyond which the motor
no longer affects the process.
Setpoint Rate Down value -
when making a setpoint change,
this is the rate at which setpoint
will change from the original
setpoint down to the new one.
Setpoint Rate Up value - when
making a setpoint change, this is
the rate at which setpoint will
change from the original setpoint
up to the new one.
Function Blocks
Value or Selection
-99999 to 99999
-99999 to 99999
0 - 5
up to 4 characters
-99999 to 99999
-99999 to 99999
-99999 to 99999
0 to 100%
0 to 100%
0 (off) to 9999
(eu/min)
0 (off) to 9999
(eu/min)
221