Table 2-13 Range/Limit Tab Configuration Parameters - Honeywell UMC800 Reference Manual

Control builder function block
Hide thumbs Also See for UMC800:
Table of Contents

Advertisement

Function Blocks
2.15 CARB Function Block,
Configuration Parameters, continued
RANGE/LIMIT TAB, continued
Properties Group
Parameter
Ranging
Display
`
Range (EU)
Limiting
SP Rate Up
50
continued

Table 2-13 Range/Limit Tab Configuration Parameters

Index#
4
PV High
range
5
PV Low
Range
Decimal
N/A
Places
N/A
Units
N/A
DEV Bar
SP High
11
Limit
SP Low
12
limit
Out High
14
Limit
Out Low
15
limit
SP Rate
35
Down
36
Function Block Reference Guide
Parameter Description
PV High Range Value
PV Low Range Value
Number of digits to display
after decimal point.
Text to display for EU
Deviation Bar Range on
Operator Interface
Setpoint High Limit Value -
prevents the local and
remote setpoints from going
above the value set here.
Setpoint Low Limit Value -
prevents the local and
remote setpoints from going
below the value set here.
Output High Limit Value - is
the highest value of output
beyond which you do not
want the automatic output
to exceed
Output Low Limit Value - is
the lowest value of output
beyond which you do not
want the automatic output
to exceed
Setpoint Rate Down value -
when making a setpoint
change, this is the rate at
which setpoint will change
from the original setpoint
down to the new one.
Setpoint Rate Up value -
when making a setpoint
change, this is the rate at
which setpoint will change
from the original setpoint up
to the new one.
Value or Selection
-99999 to 99999
-99999 to 99999
0 to 5
4 characters
-99999 to 99999
-99999 to 99999
Used for anti-soot
-99999 to 99999
-5 to 105%
-5 to 105%
0 (off) to 9999 (eu/min)
0 (off) to 9999 (eu/min)
3/99