Table 2-64 Motor Tab Configuration Parameters - Honeywell UMC800 Reference Manual

Control builder function block
Hide thumbs Also See for UMC800:
Table of Contents

Advertisement

2.74 TPSC (3POS) Function Block,
Configuration Parameters, continued
MOTOR TAB, continued
Properties
Parameter
Group
Forward Relay
Module
Output
Channel
Reverse Relay
Module
Output
Channel
Motor Data
Deadband
Traverse
Time (sec)
Example
Figure 2-78 shows a Function Block Diagram using a TPSC function block
3 position step control(without slidewire feedback) is accomplished by
assigning the motor control relays physical address under the Motor tab
section of the block configuration. See example below:
3/99

Table 2-64 Motor Tab Configuration Parameters

Index#
41
42
43
(%)
N/A
Figure 2-78 TPSC Function Block Example
Function Block Reference Guide
continued
Parameter Description
Module Number for
Forward Motor Direction
Channel Number for
Forward Motor Direction
Module Number for
Reverse Motor Direction
Channel Number for
Reverse Motor Direction
Deadband is an
adjustable gap in which
neither output operates
Motor Travel Time - the
time it takes the motor
to travel from 0 to100%
Note Motor-Relay Output Module &
Channel # assignment:
Function Blocks
Value or Selection
1 to 16
1 to 4
1 to 16
1 to 4
0.5 to 5%
0 to 1800 Seconds
INC
DEC
0601- Forward motor direction
0602 - Reverse motor direction
229