Table 2-36 Range/Limit Tab Configuration Parameters - Honeywell UMC800 Reference Manual

Control builder function block
Hide thumbs Also See for UMC800:
Table of Contents

Advertisement

Function Blocks
2.45 ON/OFF Function Block,
Configuration Parameters, continued
RANGE/LIMIT TAB, continued
Properties
Parameter
Function
Ranging
Display
Range (EU)
Limiting
SP High Limit
SP Low limit
SP Rate Up
124
continued

Table 2-36 Range/Limit Tab Configuration Parameters

Index#
PV High
0
range
1
PV Low
Range
N/A
Decimal
Places
Units
N/A
DEV Bar
N/A
6
7
9
SP Rate
Down
10
Function Block Reference Guide
Parameter Description
PV High Range Value
PV Low Range Value
Number of digits to display after
decimal point.
Text to display for EU
Deviation Bar Range on the
Operator Interface
Setpoint High Limit Value -
prevents the local and remote
setpoints from going above the
value set here.
Setpoint Low Limit Value -
prevents the local and remote
setpoints from going below the
value set here.
Setpoint Rate Down value -
when making a setpoint
change, this is the rate at which
setpoint will change from the
original setpoint down to the
new one.
Setpoint Rate Up value - when
making a setpoint change, this
is the rate at which setpoint will
change from the original
setpoint up to the new one.
Value or Selection
-99999 to 99999
-99999 to 99999
0 to 5
4 characters
-99999 to 99999
-99999 to 99999
-99999 to 99999
0 (off) to 9999 (eu/min)
0 (off) to 9999 (eu/min)
Continued next page