2.61 SPS Function Block,
SPS Block Function
The Master (SPS) block supports up to 8 ramp or soak outputs operating on a common time base. It accepts
one PV for each setpoint. Setpoint guarantee is provided for the master (SPS) block setpoints with a single
symmetrical value for each setpoint output. You can assign a failsafe value for each setpoint.
Inputs
NPGM = Program Number (when SET is ON)
NSEG = Starting Segment Number (when SET is ON)
^SET = Pulse Input to load PGM and SEG numbers
st
PV1
= 1
Process Variable
nd
PV2
= 2
Process Variable
rd
PV3
= 3
Process Variable
th
PV4
= 4
Process Variable
th
PV5
= 5
Process Variable
th
PV6
= 6
Process Variable
th
PV7
= 7
Process Variable
th
PV8
= 8
Process Variable
STRQ = for connection to the STQR output of the STSW function block.
block encodes discrete inputs to a form that will convey change mode requests from the STSW block:
0.0
1.0
2.0
4.0
8.0
16.0
32.0
Outputs
PGM = Current Program Number
SEG = Current Segment number
STA = Program State (Reset, Run, Hold, Ghold, Stop).
SP1 = Setpoint #1 Output (EU)
SP2 = Setpoint #2 Output (EU)
SP3 = Setpoint #3 Output (EU)
SP4 = Setpoint #4 Output (EU)
SP5 = Setpoint #5 Output (EU)
SP6 = Setpoint #6 Output (EU)
SP7 = Setpoint #7 Output (EU)
SP8 = Setpoint #8 Output (EU)
3/99
continued
No Change
Jog State
Guaranteed Hold State
Reset State
Hold State
Run State
Advance state
Function Block Reference Guide
Function Blocks
(See Figure
2-68) The STSW
191