Table 2-37 Alarm Tab Configuration Parameters - Honeywell UMC800 Reference Manual

Control builder function block
Hide thumbs Also See for UMC800:
Table of Contents

Advertisement

Function Blocks
2.45 ON/OFF Function Block,
Configuration Parameters, continued
ALARMS TAB, continued
Properties
Parameter
Function
Alarm 1
Setpoint 1
Setpoint 2
Alarm 2
Setpoint 1
Setpoint 2
Alarm
Hysteresis
126
continued

Table 2-37 Alarm Tab Configuration Parameters

Index#
14
Alarm 1 Setpoint 1 Value - this
is the value at which you want
the alarm type chose below to
activate
N/A
Alarm 1 Setpoint 1 Type - select
Type
what you want Alarm 1 Setpoint
1 to represent.
15
Alarm 1 Setpoint 2 Value
N/A
Alarm 1 Setpoint 2 Type
Type
16
Alarm 2 Setpoint 1 Value
Type
N/A
Alarm 2 Setpoint 1 Type
17
Alarm 2 Setpoint 2 Value
N/A
Alarm 2 Setpoint 2 Type
Type
%
22
Alarm Hysteresis in %
Function Block Reference Guide
Parameter Description
Value or Selection
-99999 to 99999 in
Engineering Units
Selections:
NO ALARM
PV_HIGH
PV_LOW
DEV_HIGH
DEV_LOW
SP_HIGH
SP_LOW
OUT_HIGH
OUT_LOW
Same as
Alarm 1 Setpoint 1
Same as
Alarm 1 Setpoint 1
Same as
Alarm 1 Setpoint 1
Same as
Alarm 1 Setpoint 1
Same as
Alarm 1 Setpoint 1
Same as
Alarm 1 Setpoint 1
0 to 5 %
Continued next page
3/99