2.26 HLLM Function Block

Description
The HLLM label stands for High Low limiter. This block is part of the Auxiliary category. It looks like this
graphically on the Control Builder:
Function
Provide high-low limit for an analog (X) value.
Turns ON H or L digital output if input exceeds or falls below set limits.
•If X < or = Low Limit value, then: OUT = LoLlM; L = ON; H = OFF.
•If X > or = High Limit value, then: OUT = HiLlM; L = OFF; H= ON.
•If X > Low Limit value and < high Limit value, then: OUT = X; L = OFF; H = OFF.
Input
X = Analog Value
Output
OUT = Analog value within limits
L = Low Limit digital indication
H= High Limit digital indication