2.15 CARB Function Block,
Configuration Parameters, continued
TUNING TAB
It looks like this graphically on the Control Builder. Table 2-14 describes the parameters and the value or
selection.
Properties Group
Parameter
Tuning
Prop Band
Constants
3/99
continued

Table 2-14 Tuning Tab Configuration Parameters

Index#
0
PB1 or
Gain 1
30
PB2 or
gain 2
or
Gain
Function Block Reference Guide
Parameter Description
Proportional Band (PB) -
is the percentage of the
range of the measured
variable for which a
proportional controller will
produce a 100% change in
its output.
Gain - is the ratio of output
change(%) over the
measured variable change
(%) that caused it.
G = 100%
PB%
where PB is the
proportional Band (in %)
Function Blocks
Value or Selection
0.1 to 1000
0.1% to 1000%
continued next page
Continued next page
51