2.4

Application: Shopping mall

2.4.1

Introduction

Shopping malls are typical example of applications with
a large number of zones with varying output power
requirements per zone. The priorities are speech
intelligibility and compliance with IEC60849 standard
(and its national equivalents)
2.4.2

Requirements

In addition to mandatory voice alarm functionality for
evacuating the public and shop personnel, an
Econtroller system for shopping centers can have BGM
for the public areas. It should be possible to individually
call each shop or store. During emergency messages, the
volume override of each individual shop is engaged.
Additional public address functionality for making
general public announcements is an optional
requirement.
table 2.7: Summary of requirements
Requirements
54 zones (typically up to 60 zones)
Speech intelligibility is the main priority
Variable power requirement per zone
Call station in security control room
Additional public address functionality
(nonemergency)
BGM in public areas
BGM music with local override in shops
2.4.3

Solution

A Plena voice alarm controller handles routing to 6
zones, the remaining 48 zones require eight 6-zone
routers. The security control room is equipped with a
remote control panel and call station plus keypads for
individually addressing zones and BGM for the public
areas, while the controller unit and routers are located
in a fire-resistant cabinet or basement. Fireman's panel
(with overall priority) is built in close to the main
entrance or emergency exit (subject to relevant local
regulations). The Plena voice alarm system is a two-
channel system, so BGM can still be provided in zones
not receiving a call.
Bosch Security Systems | 2004-06 | 9922 141 10371en
.
2.4.4

Power requirements

Each zone will have varying power requirements,
ranging from small shops with a single loudspeaker to
department stores with several floors and more
loudspeakers. Parking garages and open-air walkways
will require weatherproof sound projectors or horn
loudspeakers. To facilitate phased evacuation from
different levels of the shopping center, public areas are
divided into zones. Additional Plena booster amplifiers
are incorporated to provide additional power, two-
channel operation and for use as a spare amplifier.
table 2.8: Power requirements per zone
Zone
Description
1-30
30 small shops
31-36
6 small shops
37-42
6 medium stores
43-46
Large store, 4 levels
47
Control room
48
Offices
49
Walkways gnd floor
50
Gallery 1st floor
51
Gallery 2nd floor
52
Main public square
53
Parking level 1
54
Parking level 2
Total
2.4.5

System configuration

The Plena units, needed to build the application, are
listed in table 2.9. The interconnections are shown in
figure 2.3.
table 2.9: Used Plena units
Unit
Description
LBB1990/00
Voice alarm controller
LBB1992/00
Router
LBB1996/00
Remote control panel
LBB1997/00
RCP extension
LBB1998/00
RCP kit
LBB1999/00
RCP extension kit
LBB1956/00
Call station
LBB1957/00
CS extension keypad
LBB1935/00
240W booster
LBB1938/00
480 booster
LBB1961/00
BGM source
en | 16
Power
30x6W cab/ceil
12x6W 2/store
24x6W ceiling
16x6W ceiling
1x6W cabinet
4x6W cabinet
4x6W projector
10x6W ceiling
10x6W ceiling
4x18W horn
6x10W horn
6x10W horn
858W
Number
1x
8x
1x
8x
1x
8x
1x
5x
3x
2x
1x