Safe Parameterisation - User Responsibility; Safety-Related Configuration Parameters; Verification Procedure; If No Password Is Set - PR 9203 Manual

Solenoid / alarm driver
Table of Contents

Advertisement

Safety Manual

14 Safe parameterisation - user responsibility

14.1 Safety-related configuration parameters

Parameters
CH1.FUN
CH2.FUN.
PASSW
The above safety-related configuration parameters are marked in red
text in the routing diagrams and must be verified by the user in a SIL-
configuration.

14.2 verification procedure

The verification is done using the display / programming front PR 4501
by following the procedure described below.

14.2.1 if no password is set

1
2
3
4
5
6
7
8
9
10
* Open is shown briefly in the display.
8
9203 Solenoid / Alarm Driver
value
DIR / INV
DIR / INV
0 - 9999
action
Press OK
Set (ADV.SET) to Yes and press OK
Step down to (SIL SETUP) and press OK
Set (EN SIL) to YES and press OK
Set password to a number between 0 and
9999 and press OK
(At this time the device starts operating in
SIL mode with the entered configuration
parameters!)
Press OK to confirme verification of the
OPEN-LOCK in the display
Verify Channel 1 function and press OK
Verify Channel 2 function and press OK
Verify password and press OK
Verify SIL and press OK
description
Direct / inverted channel function
Direct / inverted channel function
New password
Version No. V3R0
display shows
ADV.SET
DISP SETUP
EN.SIL
NEW.PASS
VerifyOPEN
"briefly"
LOCK*
CH1.FUN
CH2:FUN
PASSW
SIL.OK