Timeout Monitoring Process Data Channel - BONFIGLIOLI Vectron Manual

Active cube expansion module em-res-03 230 v/400 v
Table of Contents

Advertisement

5.11.3
Each frequency inverter monitors its received data for whether they are updated
within a defined time window.
The monitoring is done onto the SYNC telegram and the RxPDO channels.
Monitoring SYNC / RxPDO's
No.
939 SYNC Timeout
941 RxPDO1 Timeout
942 RxPDO2 Timeout
945 RxPDO3 Timeout
Setting "0" means no timeout monitoring.
Attention: There is only monitoring for the SYNC telegram if at least one RxPDO or
If a timeout period is exceeded, the frequency inverter switches to failure mode and
reports one of the faults:
10/07
10/07

Timeout monitoring process data channel

Parameter
Description
one TxPDO channel is defined as SYNC controlled.
F2200
System bus Timeout SYNC
F2201
System bus Timeout RxPDO1
F2202
System bus Timeout RxPDO2
F2203
System bus Timeout RxPDO3
EM-RES-03
Min.
0 ms
0 ms
0 ms
0 ms
EM-RES-03
Setting
Max.
Fact. sett.
60000 ms
0 ms
60000 ms
0 ms
60000 ms
0 ms
60000 ms
0 ms
35
35