6.1.6
The monitoring of the analog input signal necessary according to the application is to
be configured via the parameter
The monitoring of the analog input signal is active independent of the release of the
frequency inverter according to the operation mode selected.
In operation mode 2, the drive mechanism is decelerated independent of the stopping
behavior set (Parameter
(shutdown and switch-off). If the set holding time has expired, there is a fault mes-
sage. A repeat start of the drive mechanism is possible by switching the start signal on
and off if the fault has been cleared.
Operation mode 3 defines the free stoppage of the drive mechanism, independent of
the stopping behavior selected, which is stipulated with the parameter
tion
Attention! Monitoring of the analog input signal via the parameter
58
58

Error and warning behavior

Operation mode
0 - Off
1 - Warning < 1 V / 2 mA
2 - Shutdown < 1 V / 2 mA
Fault switch-off
3 -
< 1 V / 2 mA
Operation mode
630.
Behavior
563 demands a check of the characteristic parameters.
Error/Warning behavior
The input signal is not monitored.
If the input signal is less than 1 V or 2 mA, there
is a warning message.
If the input signal is less than 1 V or 2 mA, there
is a warning message, the drive mechanism is
decelerated according to stopping behavior 1.
If the input signal is less than 1 V or 2 mA, there
is a warning and fault message and the drive me-
chanism stops freely.
630) according to stopping behavior 1
EM-RES-03
EM-RES-03
563.
Function
Stop func-
Error/Warning
10/07
10/07