Depending on the behavior of the motor after start, carry out the following steps:
Warning!
This completes the offset adjustment.
64
64
Motor does not turn, or the motor shaft only turns to a new position and
stops again:
Check if the parameters
Pairs
381 for the resolver are set correctly.
If these values are adjusted correctly, take the following measures complying with
the safety instructions.
The mains, direct voltage and motor sockets can be live with dangerous
voltage after disconnection of the frequency inverter. Work only on the
device after a waiting period of some minutes until the DC link capacitors
have discharged.
Before electrical installation work, de-energize the frequency inverter and take
appropriate precautions to make sure it is not re-energized unintentionally.
Make sure that the frequency inverter is de-energized.
Exchange two motor phases (e.g. U and V) at the frequency inverter sockets
because the senses of rotation of the motor and the resolver do not corre-
spond to each other.
Switch on the power supply again.
As described above, adjust a low speed reference value and start the motor.
If the motor does not start despite the phase exchange:
Increase the parameter value for
tor pole pairs.
If the motor still does not turn, exchange the two motor phases (e.g. U and V)
again.
The motor turns and accelerates until it reaches the
Limit
417:
Check the resolver lines and check the resolver connection contacts.
In the case of fault message "Overfrequency" F1100: increase the parameter
Offset
value for
382 by 180°, divided by the no. of motor pole pairs.
If the motor turns at the adjusted speed and in the right direction, carry
out the fine adjustment of the offset:
Adjust the parameter value for
flux-forming voltage
In case the flux-forming voltage deviates from 0 significantly, adjust the offset
in bigger steps.
In the case of a positive flux-forming voltage, increase the offset.
In the case of a negative flux-forming voltage, reduce the offset.
Frequency Switch-Off Limit
Adjust parameters
the required values.
Repeat the fine adjustment of the offset at 50% of the rated frequency.
Start the guided commissioning. This is required for optimum current control.
No. of Pole Pairs
373 for the motor and
Offset
382 by 90°, divided by the no. of mo-
Offset
382 in small steps (e.g. 2.5°) until the
235 is approximately 0.
EM-RES-03
EM-RES-03
No. of Pole
Frequency Switch-Off
Current Limit
417 and
10/07
728 to
10/07