Bypass Mode; Standby Mode; Configuration Mode - Eaton Powerware 5125 Installation Manual

For ibm applications
Hide thumbs Also See for Powerware 5125:
Table of Contents

Advertisement

OPERATION

Bypass Mode

In the event of a UPS overload or internal failure, the UPS transfers your
equipment to utility power. Battery mode is not available; however, the
utility power continues to be passively filtered by the UPS. The alarm
sounds and the
Bypass mode when:
S
S
S
S

Standby Mode

When the UPS is turned off and remains plugged into a power outlet,
the UPS is in Standby mode. The
indicators are off, indicating that power is not available to your
equipment. The battery recharges when necessary.

Configuration Mode

When the UPS is in Configuration mode, the front panel indicators
represent the configuration options. Use the control buttons
(On button, Off
configuration. Figure 24 shows the indicators and Table 9 explains the
corresponding options.
1.
NOTE If the indicators start cycling automatically from left to right, repeat Step 1 and be
sure to press both buttons.
2.
30
EATON Powerware
μ
indicator illuminates red. The UPS transfers to
The UPS has an overtemperature condition.
The UPS has an overload condition of 102 to 110% for 2 minutes.
The UPS has an overload condition >110% for 12 cycles.
The UPS detects a fault in the UPS electronics.
button, and
Press the On button and the
seconds. The UPS transfers to Configuration mode.
The indicators flash briefly and then display the enabled options.
Press the On button to scroll through the options. Each time you
press the button, the UPS beeps. The indicator for the selected
option indicates the current setting; flashing represents disabled
options (see Figure 24 and Table 9).
®
5125 (9910-E65) UPS Installation Guide for IBM
μ
indicator flashes and the load level
button) to modify the UPS
button simultaneously for three
®
S
Applications
164201698 Rev 1

Advertisement

Table of Contents
loading

Table of Contents