Requesting a Declaration of Conformity Harmonized Standards: EN 62040-1-1 and EN 62040-2; IEC 60950-1 EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage limits 93/68/EEC, Amending Directive 73/23/EEC 2004/108/EEC, Council Directive relating to electromagnetic compatibility...
Page 3
FCC Part 15 This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to NOTE part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol. CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual for additional information, such as important operating and maintenance instructions.
Chapter 1 Introduction Eaton’s Powerware 5130 uninterruptible power system (UPS) protects ® your sensitive electronic equipment from basic power problems such as power failures, power sags, power surges, brownouts, and line noise. Power outages can occur when you least expect it and power quality can be erratic.
Page 8
INTRODUCTION Providing outstanding performance and reliability, the Powerware 5130’s unique benefits include: Hours of extended runtime with up to four EBMs. Start-on-battery capability for powering up the UPS even if utility power is not available. Hot-swappable batteries that simplify maintenance by allowing you to replace batteries safely without powering down the critical load.
Chapter 2 Safety Warnings This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference. This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY.
Page 10
SAFETY WARNINGS Batteries can present a risk of electrical shock or burn from high short-circuit current. Observe proper precautions. Servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions. Keep unauthorized personnel away from batteries. Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
Batterierne kan give risiko for elektrisk stød eller brandsår forårsaget af høj kortslutningsstrøm. Overhold gældende forsigtighedsregler. Servicering skal udføres af kvalificeret servicepersonale med kendskab til batterier og gældende forsigtighedsregler. Hold uautoriseret personale væk fra batterierne. Korrekt bortskaffelse af batterier er påkrævet. Overhold gældende lokale regler for bortskaffelsesprocedurer.
Page 12
SAFETY WARNINGS Teneinde de kans op brand of elektrische schok te verminderen dient deze UPS in een gebouw met temperatuur- en vochtigheidregeling te worden geïnstalleerd, waar geen geleidende verontreinigingen aanwezig zijn. De omgevingstemperatuur mag 40°C niet overschrijden. Niet gebruiken in de buurt van water of bij zeer hoge vochtigheid (max.
Tarkeita Turvaohjeita Tämä käyttöohje sisältää tärkeitä ohjeita, joita on noudatettava UPS-virtalähteen ja akkujen asennuksen ja huollon yhteydessä. Lue kaikki ohjeet ennen laitteiston käyttöä ja säilytä ohje myöhempää tarvetta varten. Tämä UPS sisältää HENGENVAARALLISIA JÄNNITTEITÄ. Kaikki korjaukset ja huollot on jätettävä VAIN VALTUUTETUN HUOLTOHENKILÖN TOIMEKSI. UPS ei sisällä MITÄÄN KÄYTTÄJÄN HUOLLETTAVIA OSIA.
SAFETY WARNINGS Consignes de sécurité CONSIGNES DE SÉCURITÉ IMPORTANTES Ce manuel comporte des instructions importantes que vous êtes invité à suivre lors de toute procédure d’installation et de maintenance des batteries et de l’onduleur. Veuillez consulter entièrement ces instructions avant de faire fonctionner l’équipement et conserver ce manuel afin de pouvoir vous y reporter ultérieurement.
Page 15
Les batteries peuvent présenter un risque de choc électrique ou de brûlure provenant d’un courant de court-circuit haute intensité. Observez les précautions appropriées. L’entretien doit être réalisé par du personnel qualifié connaissant bien les batteries et les précautions nécessaires. N’autorisez aucun personnel non qualifié à manipuler les batteries.
SAFETY WARNINGS Um die Brand- oder Elektroschockgefahr zu verringern, diese USV nur in Gebäuden mit kontrollierter Temperatur und Luftfeuchtigkeit installieren, in denen keine leitenden Schmutzstoffen vorhanden sind. Die Umgebungstemperatur darf 40°C nicht übersteigen. Die USV nicht in der Nähe von Wasser oder in extrem hoher Luftfeuchtigkeit (max. 95 %) betreiben.
Page 17
A V V E R T E N Z A L’UPS contiene la propria fonte di energia (batterie). Le prese d’uscita possono essere sotto tensione anche quando l’UPS non è collegato all’alimentazione elettrica CA. Nei modelli da 230 V è possibile che le prese d’uscita rimangano sotto tensione. Se la fonte di alimentazione in entrata dell’installazione è...
SAFETY WARNINGS Viktig Sikkerhetsinformasion VIKTIGE SIKKERHETSINSTRUKSJONER Denne håndboken inneholder viktige instruksjoner som du bør overholde ved montering og vedlikehold av UPS-enheten og batteriene. Les alle instruksjoner før utstyret tas i bruk, og gjem håndboken til fremtidig referanse. Denne UPS’en inneholder LIVSFARLIGE SPENNINGER. All reparasjon og service må kun utføres av AUTORISERT SERVICEPERSONALE.
Batterier kan utgjøre en fare for elektrisk støt eller brannsår pga. høy kortsluttingsstrøm. Treff passende forholdsregler. Service bør utføres av kvalifisert servicepersonale med kjennskap til batterier og nødvendige forholdsregler. Hold uautorisert personale borte fra batteriene. Batterier må fjernes på korrekt måte. Se lokale forskrifter vedrørende krav om fjerning av batterier.
SAFETY WARNINGS Para reduzir o risco de incêndios ou choques elétricos, instale a UPS em ambiente interno com temperatura e umidade controladas e livres de contaminadores condutíveis. A temperatura ambiente não deve exceder 40°C. Não opere próximo a água ou em umidade excessiva (máx: 95%).
Page 21
SAFETY WARNINGS П Р Е Д У П Р Е Ж Д Е Н И Е ° О С Т О Р О Ж Н О ® EATON Powerware 5130 Rack/Tower UPS (1250–3000 VA) User’s Guide 164201730 Rev 2 www.powerware.com...
SAFETY WARNINGS Advertencias de Seguridad INSTRUCCIONES DE SEGURIDAD IMPORTANTES Este manual contiene instrucciones importantes que debe seguir durante la instalación y el mantenimiento del SIE y de las baterías. Por favor, lea todas las instrucciones antes de poner en funcionamiento el equipo y guarde este manual para referencia en el futuro. Este SIE contiene VOLTAJES MORTALES.
Page 23
Las baterías pueden constituir un riesgo de descarga eléctrica o quemaduras por corriente alta de corto circuito. Adopte las precauciones debidas. Personal calificado de servicio que conozca de baterías y esté al tanto de las precauciones requeridas debe darle servicio al equipo. Mantenga al personal no autorizado alejado de las baterías. Es necesario desechar las baterías de un modo adecuado.
Page 24
SAFETY WARNINGS Minska risken för brand eller elektriska stötar genom att installera denna UPS-enhet inomhus, där temperatur och luftfuktighet är kontrollerade och där inga ledande föroreningar förekommer. Omgivande temperatur får ej överstiga 40°C. Använd inte utrustningen nära vatten eller vid hög luftfuktighet (max 95 %). För att överensstämma med internationell standard och installationsföreskrifter får inte den totala utrustning som anslutits till uttagen på...
Chapter 3 Installation This section explains: Equipment inspection UPS internal battery connection UPS setup and installation, including Extended Battery Modules (EBMs) Remote power-off (RPO) or remote on/off (ROO) installation UPS rear panels Inspecting the Equipment If any equipment has been damaged during shipment, keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage.
INSTALLATION Checking the Accessory Kit Verify that the following additional items are included with the UPS: Table 1. UPS Accessory Kit Item ® EATON Powerware 5130 Rack/Tower UPS (1250–3000 VA) User’s Guide www.powerware.com Description UPS user’s guide or CD Quick start instructions UPS front cover USB cable RS-232 serial cable...
Page 27
The high-voltage models include the following additional items: Table 2. Additional High-Voltage Model Accessory Items Item Description Two cord-retention brackets Two equipment power cords 2500–3000 VA models only. Power cord If you ordered an optional EBM, verify that the following items are included with the EBM: Table 3.
INSTALLATION Connecting the UPS Internal Battery To ensure proper battery operation: Verify that the UPS is off and unplugged. Connect the internal battery connectors by firmly pressing the connectors together (see Figure 2). NOTE A small amount of arcing may occur when connecting the batteries. This is normal and does not damage the unit or present any safety concern.
UPS Setup The Powerware 5130 UPS is designed for flexible configurations and can be installed in a rack or as a standalone cabinet. If you are installing the UPS in a rack, continue to the following section, “Rackmount Setup;” otherwise, continue to “Tower Setup” on page 25. Rackmount Setup The rail kit can be mounted in 19-inch panel (48 cm) racks from 24 to 30 inches (61 to 76 cm) deep and includes:...
INSTALLATION Installing the Rail Kit The UPS and EBM are heavy (see page 52). A minimum of two people are required to lift the cabinets into the rack. NOTE Mounting rails are required for each UPS and EBM cabinet. If mounting rails are not already installed in your rack, contact your local distributor to order rail kits.
Place the UPS on a flat, stable surface with the front of the UPS facing you. Attach the supplied mounting brackets to the cabinet and secure with four M4 screws on each side (see Figure 4). If installing optional EBMs, repeat Steps 1 and 7 for each cabinet. NOTE The UPS and EBMs MUST be installed at the bottom of the rack.
Page 32
INSTALLATION For one 2U cabinet, the pedestals must be installed. Continue to Step 3. For one 3U cabinet, continue to “Installing the UPS” on page 28. For two or more cabinets, the joining brackets must be installed. Skip to Step 5. Align the pedestals with the screw holes on the sides of the UPS cabinet.
Page 33
Align each joining bracket with the adjacent cabinet screw holes and secure with the supplied screws (see Figure 7). NOTE Joining brackets are required for installations with two or more cabinets. Figure 7. Installing the Joining Brackets If installing additional EBMs, repeat Step 5 for each cabinet. Continue to the following section, “Installing the UPS.”...
INSTALLATION Installing the UPS NOTE Do not make unauthorized changes to the UPS or accessories; otherwise, damage may occur to your equipment and void your warranty. See “UPS Rear Panels” on page 33 for the rear panel of each model. To install the UPS and optional EBMs: If installing an optional EBM, continue to Step 2;...
Page 35
If you plan to install power management software, connect your computer to the USB port or RS-232 communication port using the supplied communication cable. Figure 9. Installing a Communication Cable For rackmount installations only. If your rack has conductors for grounding or bonding of ungrounded metal parts, connect the ground cable (not included) to the ground bonding screw.
Page 36
INSTALLATION Plug the equipment to be protected into the appropriate UPS output receptacles (see page 42 for more information on load segments). See Figure 10. NOTE DO NOT protect laser printers with the UPS because of the exceptionally high power requirements of the heating elements.
RPO and ROO Installation The Powerware 5130 includes a two-position terminal (see Figure 11) that can be either left closed or configured one of two ways: RPO: Allows a remote contact to be used to disconnect all equipment connected to the UPS. Restarting the UPS requires manual intervention.
Page 38
INSTALLATION The RPO/ROO circuit is an IEC 60950 safety extra low voltage (SELV) circuit. This circuit must be separated from any hazardous voltage circuits by reinforced insulation. To install the RPO or ROO switch: Verify that the UPS is off and unplugged. Unscrew and remove the RPO/ROO connector from the RPO/ROO port on the UPS rear panel.
UPS Rear Panels This section shows the rear panels of the Powerware 5130 models. USB Port RS-232 Port Communication Bay EBM RJ-11 Connector Site Fault Indicator RPO/ROO Connector Figure 12. 1250–1750 VA, Low-Voltage Rear Panel USB Port RS-232 Port Communication Bay EBM RJ-11 Connector Site Fault Indicator...
Page 40
INSTALLATION USB Port RS-232 Port Communication EBM RJ-11 Connector RPO/ROO Connector USB Port RS-232 Port Communication EBM RJ-11 Connector RPO/ROO Connector Figure 15. 1250–1750 VA, High-Voltage Rear Panel USB Port RS-232 Port Communication EBM RJ-11 Connector RPO/ROO Connector Figure 16. 2500–3000 VA, High-Voltage Rear Panel ®...
Chapter 4 Operation This section describes: Turning the UPS on and off Starting the UPS on battery Initiating the self-test Operating modes Turning the UPS On To turn the UPS on: Plug the UPS power cord into a power outlet. Standby mode.
OPERATION Starting the UPS on Battery NOTE Before using this feature, the UPS must have been powered by utility power at least once. To turn on the UPS without using utility power, press and hold the button for two seconds. The UPS starts up in Battery mode and supplies battery power to your equipment.
Operating Modes The Powerware 5130 front panel indicates the UPS status through the UPS indicators. Figure 17 shows the UPS front panel indicators and controls. Load Level Indicators Battery Charge Level Indicators Normal Mode During Normal mode, the the front panel displays the percentage of UPS load capacity being used by the protected equipment (see Figure 18).
OPERATION Battery Mode When the UPS is operating during a power outage, the alarm beeps once every 10 seconds and the are on. The power. When utility power returns, the UPS transfers to Normal mode operation while the battery recharges. If battery capacity becomes low while in Battery mode, the alarm beeps every three seconds.
Chapter 5 Additional UPS Features This section describes: USB port RS-232 communication port Communication card Load segments (PowerShare) The Powerware 5130 UPS includes a USB port, a RS-232 communication port, and a bay for an optional communication card. The USB and RS-232 ports cannot operate simultaneously. USB Port The UPS can communicate with a USB-compliant computer using Powerware LanSafe...
Page 46
ADDITIONAL UPS FEATURES Install the Powerware LanSafe Power Management Software and USB drivers according to the instructions provided at www.powerware.com. ® EATON Powerware 5130 Rack/Tower UPS (1250–3000 VA) User’s Guide www.powerware.com Figure 20. The USB Port 164201730 Rev 2...
Contact Communication Port (optional) When a signal is activated, the contact is closed between the common (Pin 4) and the pin for the corresponding signal. Contact characteristics (optocoupler): Voltage: 48 V DC max Current: 25 mA max Power: 1.2W Figure 21 identifies the cable pins and Table 4 describes the pin functions.
ADDITIONAL UPS FEATURES Load Segments (PowerShare) Each UPS has programmable outlets as shown in Figure 22 through Figure 24. During a power outage, you can keep key pieces of equipment running while you turn off other equipment. It is preferable to connect the non-priority loads to the programmable receptacles, feature allows you to save battery power.
Customizing the UPS with the UPS Configuration Tool To customize the UPS settings: Download the UPS Configuration tool from www.powerware.com. Follow the on-screen instructions for the Powerware 5130. It is possible to modify the settings listed below (detailed comments are available in the UPS Configuration tool). Table 5.
Page 50
ADDITIONAL UPS FEATURES Table 6. Voltage Threshold Options (continued) PW5130G3000-XL2U Function High threshold for transfer to battery Low threshold for transfer to battery Fader activation threshold Booster activation threshold Maximum input-voltage range Low threshold for transfer to battery is 150V. Table 7.
Chapter 6 UPS Maintenance This section explains how to: Care for the UPS and batteries Transport the UPS Store the UPS and batteries Replace the batteries Test new batteries Recycle used batteries or UPS UPS and Battery Care For the best preventive maintenance, keep the area around the UPS clean and dust-free.
UPS MAINTENANCE Storing the UPS and Batteries If you store the UPS for a long period, recharge the battery every 6 months by plugging the UPS into a power outlet. The batteries charge to 90% capacity in approximately 3 hours. However, it is recommended that the batteries charge for 24 hours after long-term storage.
How to Replace Internal Batteries Pull the battery out onto a flat, stable surface. The battery is unsupported when you pull it out of the UPS. To ensure safety and high performance, use only batteries supplied by Eaton. To replace the UPS internal batteries: Remove the UPS front cover.
Page 54
UPS MAINTENANCE Unscrew and remove the metal battery cover (see Figure 27). Pull the battery block out onto a flat, stable surface (see Figure 28). See “Recycling the Used Battery or UPS” on page 50 for proper disposal. Install the new batteries in the reverse order of removal. Replace the metal battery cover.
How to Replace Extended Battery Modules To replace the Extended Battery Modules (EBMs): Unplug the EBM cable from the UPS. If additional EBMs are installed, unplug the EBM cable from the battery connector on each EBM. Unplug the EBM communication cable from the RJ-11 port. Repeat for each EBM.
UPS MAINTENANCE Replace the EBM. See “Recycling the Used Battery or UPS” on page 50 for proper disposal. For tower models only. Install the joining bracket between cabinets. Plug the new EBM into the UPS as shown in Figure 29. For additional EBMs, plug the EBM cable into the battery connector on the adjacent EBM.
Chapter 7 Specifications Filter Table 10. Low-Voltage Model Specifications Power Levels Model Number (Rated at Nominal Inputs) PW5130L1250-XL2U 1250 VA, 1150W PW5130L1750-XL2U 1750 VA, 1600W PW5130L2500-XL2U 2500 VA, 2250W PW5130L3000-XL2U 2880 VA, 2700W PW5130L3000-XL3U The high and low thresholds can be adjusted using the UPS Configuration tool (see page 43). Up to 40 Hz in low-sensitivity mode (programmable using the UPS Configuration tool).
Page 58
SPECIFICATIONS Table 11. High-Voltage Model Specifications Power Levels Model Number (Rated at Nominal Inputs) PW5130i1250-XL2U 1250 VA, 1150W PW5130i1750-XL2U 1750 VA, 1600W PW5130i2500-XL2U 2500 VA, 2250W PW5130i3000-XL2U 3000 VA, 2700W PW5130i3000-XL3U PW5130G3000-XL2U 3000 VA, 2700W The high and low thresholds can be adjusted using the UPS Configuration tool (see page 43). Up to 40 Hz in low-sensitivity mode (programmable using the UPS Configuration tool).
Page 59
Table 12. Weights and Dimensions (continued) EBM Model Number PW5130N1750-EBM2U PW5130N3000-EBM2U PW5130N3000-EBM3U Table 13. Power Connections Model PW5130L1250-XL2U 6 ft, 15A, 5-15P power cord PW5130L1750-XL2U 6 ft, 20A, 5-20P power cord PW5130L2500-XL2U PW5130L3000-XL2U 6 ft, 30A, L5-30P power cord PW5130L3000-XL3U PW5130i1250-XL2U 10A, IEC-C14 input connector PW5130i1750-XL2U...
Page 60
SPECIFICATIONS Table 14. Environmental and Safety Low Voltage Models Operating Temperature Storage Temperature Relative Humidity Audible Noise Surge Suppression Safety Conformance UL 1778, UL 497A; CSA C22.2, No. 107.1; NOM-019-SCFI Agency Markings FCC Part 15 Class A Table 15. Battery UPS Configuration EBM Configuration PW5130N1750-EBM2U: 48 Vdc, (2 stings of 4) 12V, 9 Ah batteries...
Page 61
Table 16. Battery Runtimes Half Load UPS Internal Batteries 1250 VA/575W 15 min 22 sec 1750 VA/800W 9 min 35 sec 2500 VA/1125W 11 min 15 sec 3000 VA/2700W 10 min 15 sec Full Load UPS Internal Batteries 1250 VA/1150W 5 min 1750 VA/1600W 3 min 30 sec...
Chapter 8 Troubleshooting This section explains: UPS alarms and conditions Service and support Audible Alarms and UPS Conditions The UPS has an audible alarm feature to alert you of potential power problems. Use Table 17 to determine and resolve the UPS alarms and conditions.
Page 64
TROUBLESHOOTING Table 17. Troubleshooting Guide Alarm or Condition Possible Cause The remote power-off (RPO) When starting the UPS with the contact has been activated to button, all the indicators turn on once, the alarm beeps once, and shut down the UPS and now then indicator remains on.
Service and Support If you have any questions or problems with the UPS, call your Local Distributor or the Help Desk at one of the following telephone numbers and ask for a UPS technical representative. United States: Canada: All other countries: Please have the following information ready when you call the Help Desk: Model number...
Two-Year Limited Warranty (US and Canada) Powerware UPS Models: 5110, 5115, 5125, and 5130 WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Electrical, Inc., a Delaware Corporation company (“Company”). LIMITED WARRANTY: This limited warranty (this “Warranty”) applies only to the original End-User (the “End-User”) of any Powerware 5110, 5115, 5125, and 5130 Products (individually and collectively, the “Product”) purchased on...
Page 68
WARRANTY WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages caused by: (a) failure to properly store the Product before installation, including the charge of batteries no later than the date indicated on the packaging; (b) shipping and delivery of the Product if shipping is FOB Factory; (c) neglect, accident, abuse, misuse, misapplication, or incorrect installation;...
Ten-Year Pro-Rated Limited Warranty (US and Canada) Powerware UPS Models: 5115, 5125, 5130, 5140, 9120, 9125, 9155, 9170+, and FERRUPS WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Electrical Inc., a Delaware Corporation company (“Company”). LIMITED WARRANTY: This pro-rated limited warranty (this “Warranty”) applies only to the original End-User (the...
Page 70
WARRANTY WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages caused by: (a) failure to properly store the Product before installation, including the charge of batteries no later than the date indicated on the packaging; (b) shipping and delivery of the Product if shipping is FOB Factory; (c) neglect, accident, abuse, misuse, misapplication, or incorrect installation;...
Load Protection Guarantee (US and Canada) Powerware UPS Models 3105, 5110, 5115, 5125, 5130, 9120, 9125, 9150, 9155, 9170+, and FERRUPS GUARANTOR: The Guarantor for the load protection guaranty set forth herein is Eaton Electrical Inc., a Delaware Corporation company (“Company”). LIMITED GUARANTY: This load protection guaranty (this “Guaranty”) applies only to the original End-User (the...
Page 72
WARRANTY WHAT THIS GUARANTY DOES NOT COVER: Any reimbursement or repair to End-User’s equipment does not include reimbursement for or restoration of any data loss. This Guaranty does not cover any defects or damages caused by: (a) failure to properly store the Product before installation, including the charge of batteries no later than the date indicated on the packaging;...