OPERATION
Table 9. Configuration Mode Indicators and Options
Configuration Mode
Option
Indicators
200/208V
Nominal Output
V l
Voltage
220V Nominal
Output Voltage
p
230V Nominal
Output Voltage
p
240V Nominal
Output Voltage
p
Site Wiring
Fault Alarm
0 EBMs
1 EBM
2 EBMs
32
EATON Powerware
Indicator
Explanation
Status
On
Selecting this option changes the nominal output voltage to
p
(default)
200/208V.
Flashing
200/208V is disabled; one of the other output voltage options is
selected.
On
Selecting this option changes the nominal output voltage to
g
220V.
Flashing
220V is disabled; one of the other output voltage options is
selected.
On
Selecting this option changes the nominal output voltage to
g
230V.
Flashing
230V is disabled; one of the other output voltage options is
selected.
On
Selecting this option changes the nominal output voltage to
g
240V.
Flashing
240V is disabled; one of the other output voltage options is
selected.
On
Alarm sounds when the polarity of the outlet is reversed or the
ground connection is missing; have a qualified electrician
repair the outlet wiring.
Flashing
Alarm DOES NOT sound when the polarity of the outlet is
(default)
reversed or the ground connection is missing.
On
Zero EBMs are configured.
(default)
Flashing
One of the other EBM configurations is selected.
On
One EBM is configured.
Flashing
One of the other EBM configurations is selected.
On
Two EBMs are configured.
Flashing
One of the other EBM configurations is selected.
®
5125 (9910-E65) UPS Installation Guide for IBM
®
S
Applications
164201698 Rev 1