Operator Parameters
ID:
Name:
Meaning
Parameter number (PNU):
Subindex:
Data type:
Coding:
Standard value:
Note:
(*1): In case of full duplex services the PDOUT data are transferred in Request to the frequency inverter con-
trol and Response contains the PDIN data. PDOUT data and PDIN data are independently transferred
at non-full duplex services. The outcome of this at full duplex services is that the values for PDOUT_
Hsp5Service/ PDOUT2_Hsp5Service and PDIN_Hsp5Service/ PDIN2_Hsp5Service must be identical.
32
Fb06
PDIN1_Hsp5Service
The adjustment of this parameter is only relevant for the normal mode. Indicates
the service code for the KEB internal protocol HSP5 to read the first 8 PDIN
data-byte from the operator to the frequency inverter control.
The value must be suitable adjusted to the PDIN mapping in the frequency
inverter.
0286h
0
Uint8
16: PDIN assignment only with 32 bit values
17: PDIN assignment only with 16 bit values
48: PDIN assignment only with 32 bit values, full duplex (*1)
49: PDIN assignment only with 16 bit values, full duplex (*1)
50: PDIN assignment with 1 32-bit- and 1-2 16-bit values, full duplex (*1)
17
A changed value is stored immediately active and non-volatile.This parameter is
write protected, if Fb01 FBS Config.Bit5 is 1.