KEB COMBIVERT F5 Instruction Manual page 31

Profinet operator
Hide thumbs Also See for COMBIVERT F5:
Table of Contents

Advertisement

ID:
Name:
Meaning
Parameter number (PNU):
Subindex:
Data type:
Coding:
Standard value:
Note:
ID:
Name:
Meaning
Parameter number (PNU):
Subindex:
Data type:
Coding:
Standard value:
Note:
ID:
Name:
Meaning
Parameter number (PNU):
Subindex:
Data type:
Coding:
Standard value:
Note:
Fb03
RealSyncCycleTime
Specifies the determined synchronous cycle time of the F5 PROFINET opera-
tor. The calculation of this time is updated with each Sync signal.
0283h
0
Uint16
1 µs
This parameter is read-only.
Fb04
FBS Command
Certain commands in the F5 PROFINET operator can be requested via this
parameter. After execution of the command the operator sets bit 15 of the value
to 1.
0284h
0
Uint16
0: no command
1: Sets all non-volatile stored parameters of the operator to default values.
0
Fb05
PDOUT1_Hsp5Service
The adjustment of this parameter is only relevant for the normal mode. Indicates
the service code for the KEB internal protocol HSP5 to output the first 8 PDOUT
data-byte from the operator to the frequency inverter control. The value must be
suitable adjusted to the PDOUT mapping in the frequency inverter.
0285h
0
Uint8
16: PDOUT assignment only with 32 bit values
17: PDOUT assignment only with 16 bit values
48: PDOUT assignment only with 32 bit values, full duplex(*1)
49: PDOUT assignment only with 16 bit values, full duplex(*1)
50: PDOUT assignment with 1 32-bit- and 1-2 16-bit values, full duplex (*1)
17
A changed value is stored immediately active and non-volatile.This parameter is
write protected, if Fb01 FBS Config.Bit5 is 1.
31