6. Application Examples

6.1.7. SLC Application Example

One sequence 1:
Start – ramp up – run at reference speed 2 sec – ramp down and hold shaft until stop.
6
Set the ramping times in par. 3-41 and 3-42 to the wanted times
t acc
×
t ramp
=
Set term 27 to
No Operation
Set Preset reference 0 to first preset speed (par. 3-10 [0]) in percentage of Max reference speed (par. 3-03). Ex.: 60%
Set preset reference 1 to second preset speed (par. 3-10 [1] Ex.: 0 % (zero).
Set the timer 0 for constant running speed in par. 13-20 [0]. Ex.: 2 sec.
Set Event 1 in par. 13-51 [1] to
Set Event 2 in par. 13-51 [2] to
Set Event 3 in par. 13-51 [3] to
Set Event 4 in par. 13-51 [1] to
Set Action 1 in par. 13-52 [1] to
Set Action 2 in par. 13-52 [2] to
Set Action 3 in par. 13-52 [3] to
Set Action 4 in par. 13-52 [4] to
116
n norm
(
par
. 1 − 25 )
ref RPM
Δ
(par. 5-12)
True
[1]
On Reference
[4]
Time Out 0
[30]
False
[0]
Select preset 0
[10]
Start Timer 0
[29]
Select preset 1
[11]
No Action
[1]
MG.20.N3.02 - VLT
®
is a registered Danfoss trademark
®
VLT
AQUA Drive Design Guide