2. Introduction to VLT AQUA Drive
2.10.2. EMC Test Results (Emission, Immunity)
The following test results have been obtained using a system with a frequency converter (with options if relevant), a screened control cable, a
control box with potentiometer, as well as a motor and motor screened cable.
RFI filter type
2
Setup
H1
0.25-45 kW 200-240 V
0.25-90 kW 380-480 V
H2
0.25-3.7 kW 200-240 V
5.5-45 kW 200-240 V
0.25-7.5 kW 380-480 V
11-90 kW 380-480 V
H3
0.25-45 kW 200-240 V
0.25-90 kW 380-480 V
Table 2.1: EMC Test Results (Emission, Immunity)
1) 11 kW 200 V, H1 and H2 performance is delivered in enclosure type B1.
11 kW 200 V, H3 performance is delivered in enclosure type B2.
2.10.3. Required Compliance Levels
Standard / environment
IEC 61000-6-3 (generic)
IEC 61000-6-4
EN 61800-3 (restricted)
EN 61800-3 (unrestricted)
EN 55011:
Class A1:
Class A2:
Class B1:
2.10.4. EMC Immunity
In order to document immunity against electrical interference from electrical phenomena, the following immunity tests have been made on a system
consisting of a frequency converter (with options, if relevant), a screened control cable, and a control box with potentiometer, motor cable, and motor.
The tests were performed in accordance with the following basic standards:
•
EN 61000-4-2 (IEC 61000-4-2): Electrostatic discharges
•
EN 61000-4-3 (IEC 61000-4-3): Incoming electromagnetic field radiation, amplitude
and radio communication equipment as well as mobile communications.
•
EN 61000-4-4 (IEC 61000-4-4): Burst
devices.
•
EN 61000-4-5 (IEC 61000-4-5): Surge
•
EN 61000-4-6 (IEC 61000-4-6): RF Common
cables.
See following EMC immunity form.
32
Conducted emission
Industrial environment
EN 55011 Class A2 EN 55011 Class
150 m
150 m
5 m
25 m
5 m
25 m
75 m
75 m
Housing, trades, and light industries
Conducted
Class B
Class A1
Class B
Threshold values and measuring methods for radio interference from industrial, scientific and
medical (ISM) high-frequency equipment.
Equipment used in a public supply network. Restricted distribution.
Equipment used in a public supply network.
Equipment used in areas with a public supply network (dwellings, commerce, and light industries).
Unrestricted distribution.
transientsSimulation of interference brought about by switching with a contactor, relays, or similar
transientsSimulation of transients brouht e.g. by lightning that strikes near installations.
MG.20.N3.02 - VLT
Housing, trades
and light industries
EN 55011 Class B
A1
150 m 1)
50 m
150 m
50 m
No
No
No
No
No
No
No
No
50 m 1)
10 m
50 m
10 m
Radiated
Class B
Class A1
Class B
(ESD)Simulation of electrostatic discharges from human beings.
modeSimulation of the effect from radio-transmitting equipment connected to connection
®
is a registered Danfoss trademark
®
VLT
AQUA Drive Design Guide
Radiated emission
Industrial environ-
Housing, trades and light
ment
industries
EN 55011 Class A1
EN 55011 Class B
Yes
No
Yes
No
No
No
No
No
No
No
No
No
Yes
No
Yes
No
Industrial environment
Conducted
Radiated
Class A1
Class A1
Class A1
Class A1
Class A2
Class A2
modulatedSimulation of the effects of radar