Danfoss VLT AQUA Design Manual page 33

Hide thumbs Also See for VLT AQUA:
Table of Contents

Advertisement

®
VLT
AQUA Drive Design Guide
VLT AQUA; 200-240 V, 380-480 V
Basic standard
Acceptance criterion
Line
Motor
Brake
Load sharing
Control wires
Standard bus
Relay wires
Application and Fieldbus options
LCP cable
External 24 V DC
Enclosure
AD: Air Discharge
CD: Contact Discharge
CM: Common mode
DM: Differential mode
1. Injection on cable shield.
Table 2.2: Immunity
Burst
Surge
IEC 61000-4-4
IEC 61000-4-5
B
B
2 kV/2 Ω DM
4 kV CM
4 kV/12 Ω CM
4 kV CM
4 kV/2 Ω
1)
4 kV CM
1)
4 kV/2 Ω
4 kV CM
1)
4 kV/2 Ω
2 kV CM
2 kV/2 Ω
1)
2 kV CM
2 kV/2 Ω
1)
2 kV CM
2 kV/2 Ω
1)
2 kV CM
2 kV/2 Ω
1)
2 kV CM
2 kV/2 Ω
1)
0.5 kV/2 Ω DM
2 kV CM
1 kV/12 Ω CM
®
MG.20.N3.02 - VLT
is a registered Danfoss trademark
2. Introduction to VLT AQUA Drive
ESD
Radiated electromagnetic field
IEC 61000-4-2
IEC 61000-4-3
B
A
8 kV AD
10 V/m
6 kV CD
RF common
mode voltage
IEC 61000-4-6
A
10 V
RMS
10 V
2
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
33

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT AQUA and is the answer not in the manual?

Table of Contents