Parameter list

3.6.2
Parameter list
indicates simple mode parameters..
......V/F control,
V/F
V/F
V/F
.....General-purpose magnetic flux vector control
GP MFVC
GP MFVC
GP MFVC
(Parameters without any indication are valid for all control.)
" " indicates enabled and "x" indicates disabled of "parameter copy", "parameter clear", and "all parameter clear".
Parameter
Function
0
Torque boost
Second torque
46
boost
Maximum
1
frequency
Minimum
2
frequency
High speed
maximum
18
frequency
3
Base frequency
Base frequency
19
voltage
Second V/F (base
47
frequency)
Multi-speed setting
4
(high speed)
Multi-speed setting
5
(middle speed)
Multi-speed setting
6
(low speed)
24
Multi-speed setting
to
(4 speed to 7 speed)
27
Multi-speed setting
232
(8 speed to 15
to
239
speed)
74
......Advanced magnetic flux vector control
AD MFVC
AD MFVC
AD MFVC
Incre-
Initial
Name
ments
Value
6/4/3/
0.1%
2% ∗
0.1%
9999
0.01Hz 120Hz 0 to 120Hz Upper limit of the output frequency.
0.01Hz
0Hz
0.01Hz 120Hz
0.01Hz
60Hz
0.1V
9999
0.01Hz
9999
0.01Hz
60Hz
0.01Hz
30Hz
0.01Hz
10Hz
0.01Hz
9999
0.01Hz
9999
Range
Description
Set the output voltage at 0Hz as %.
0 to 30%
The setting depends on the inverter capacity.
(0.1K to 0.75K/1.5K to 3.7K/5.5K, 7.5K/11K, 15K)
0 to 30%
Torque boost when the RT signal is ON.
9999
Without second torque boost
0 to 120Hz Lower limit of the output frequency.
120 to
Set when performing the operation at
400Hz
120Hz or more.
Rated motor frequency.
0 to 400Hz
(50Hz/60Hz)
0 to 1,000V Base voltage.
95% of power supply voltage
8888
(95% of doubled power supply voltage for
single-phase 100V power input model.)
Same as power supply voltage
9999
(Twice the amount of power supply voltage
for single-phase 100V power input model.)
0 to 400Hz Base frequency when the RT signal is ON.
9999
Second V/F invalid
0 to 400Hz Frequency when RH turns ON.
0 to 400Hz Frequency when RM turns ON.
0 to 400Hz Frequency when RL turns ON.
0 to 400Hz
Frequency from 4 speed to 15 speed can
9999
be set according to the combination of the
RH, RM, RL and REX signals.
0 to 400Hz,
9999: not selected
9999
All
Param
Param
Param
eter
eter
eter
Copy
Clear
Clear

Hide quick links: