Parameter
Function
Name
Motor excitation
82
current
Rated motor
83
voltage
Rated motor
84
frequency
Motor constant
90
(R1)
Motor constant
91
(R2)
Motor constant
92
(L1)
Motor constant
93
(L2)
Motor constant (X)
94

Auto tuning

96
setting/status
Torque current
859
89
Refer to Pr.81.
90 to 94
Refer to Pr.82 to Pr.84.
——
96
Refer to Pr.82 to Pr.84.
Incre-
Initial
Range
ments
Value
Tuning data (The value measured by
offline auto tuning is automatically set.)
0 to 500A∗
* The range differs according to the Pr. 71 setting.
0.01A∗
9999
(
Manual (applied)).
Uses the Mitsubishi motor (SF-JR, SF-HR,
9999
SF-JRCA, SF-HRCA) constants
Rated motor voltage (V).
200V/
0.1V
0 to 1,000V
* Differs according to the voltage class (100V,
400V ∗
200V/400V)
10 to
0.01Hz
60Hz
Rated motor frequency (Hz).
120Hz
Tuning data (The value measured by
offline auto tuning is automatically set.)
0.001Ω
9999
* The range differs according to the Pr.71 setting.
0 to 50Ω∗,
(
Manual (applied)).
9999
9999: Use constants of the Mitsubishi
0.001Ω
9999
motor (SF-JR, SF-HR, SF-JRCA, SF-
HRCA)
Tuning data (The value measured by
offline auto tuning is automatically set.)
0.1mH∗
9999
* The range differs according to the Pr.71 setting.
0 to
(
1000mH∗,
Manual (applied)).
9999
9999: Use constants of the Mitsubishi
0.1mH∗
9999
motor (SF-JR, SF-HR, SF-JRCA, SF-
HRCA)
Tuning data (The value measured by
offline auto tuning is automatically set.)
0 to 100%∗
* The range differs according to the Pr.71 setting.
0.1%∗
9999
(
Manual (applied)).
Use the Mitsubishi motor (SF-JR, SF-HR,
9999
SF-JRCA, SF-HRCA) constants
0
Offline auto tuning is not performed
For Advanced magnetic flux vector control
1
Offline auto tuning is performed without
motor running (all motor constants)
For General-purpose magnetic flux vector
control
11
1
0
Offline auto tuning is performed without
motor running(motor constant (R1) only)
Offline auto tuning for V/F control
(automatic restart after instantaneous
power failure (with frequency search))
21
(
Manual (applied))
Tuning data (The value measured by
offline auto tuning is automatically set.)
0 to 500A∗
* The range differs according to the Pr.71 setting.
0.01A∗
9999
(
Manual (applied)).
Use the Mitsubishi motor (SF-JR, SF-HR,
9999
SF-JRCA, SF-HRCA) constants
Parameter list
Description
Refer to the chapter 4 of the Instruction
Refer to the chapter 4 of the Instruction
Refer to the chapter 4 of the Instruction
Refer to the chapter 4 of the Instruction
Refer to the chapter 4 of the Instruction
Refer to the chapter 4 of the Instruction
All
Param
Param
Param
eter
eter