Controllable Double Point (Dpc) - ABB COM600 User Manual

Station automation, 3.4, dnp 3.0 lan/wan slave (opc)
Hide thumbs Also See for COM600:
Table of Contents

Advertisement

1MRS755496
3.4.5.9.
Station Automation COM600 3.4
DNP 3.0 LAN/WAN Slave (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Unit
Default: Dimensionless

Controllable double point (DPC)

Table 3.4.5.9-1 Configurable DPC properties
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
DPC
Class
Addresses
Control Index Close
-1 to 65535
Default: -1
Control Index Open
-1 to 65535
Default: -1
Index 52a
-1 to 65535
Default: 11
Index 52b
-1 to 65535
Default: 12
Index BFI
-1 to 65535
Default: 12
Data Class Spe-
cific
Control Code Quali-
Momentary
fier
Latched
Pulsed
Default: Momentary
Control Object
Binary control output block
(12).
Control Variation
0 to 65535
Indication Object
Binary input (1, 2)
Binary output (10)
Default: Binary input (1, 2)
Description
SI unit for measurement as described in
IEC61850
Description
Common data class according to IEC
61850.
Index for Control Close command.
Index for Control Open command.
Index for 52a.
Index for 52b.
Index for Breaker Failure Indication.
Qualifier for control.
Object number for control.
Variation for control
Object number for indication.
29

Advertisement

Table of Contents
loading

Table of Contents