1MRS755496
3.4.5.6.
3.4.5.7.
Station Automation COM600 3.4
DNP 3.0 LAN/WAN Slave (OPC) User's Manual
Binary controlled step position information (BSC)
Table 3.4.5.6-1 Configurable BSC properties
Property/ Parameter
Value or Value range/
Default
Basic
Common Data Class
BSC
Addresses
Control Index
-1 to 65535
Default: -1
Indication Index
-1 to 65535
Default: -1
Data Class Specific
Control Code Qualifier
Momentary
Latched
Pulsed
Default: Momentary
Control Variation
0 to 65535
Operate
Direct Operate
Select Before Operate
Default: Direct Operate
Complex measured value (CMV)
Table 3.4.5.7-1 Configurable CMV properties
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
CMV
Class
Addresses
Index
-1 to 65535
Default: -1
Sub-Type
Subtype
Simple
Description
Common data class according to IEC 61850.
Control index.
Indication index.
Qualifier for control.
Variation for control
Specifies using two-step, select-before-operate
method for issuing control request or not.
Description
Common data class according to IEC
61850.
Indication index.
MV sub-type
27