DNP 3.0
LAN/WAN Master
(OPC) 3.2
3.4.8.5.
3.4.8.6.
32
COM600 Station Automation Series
User's Guide
Property/ Para-
Value or Value range/ Default
meter
Data Class Spe-
cific
Control Variation
0 to 65535
Default: 2
Binary counter reading (BCR)
Table 3.4.8.5-1 Configurable BCR properties for OPC client
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
BCR
Class
Addresses
Indication Index
-1 to 65535
Default: -1
Data Class Spe-
cific
Counter Object
Binary counter (20)
Frozen counter (21)
Default: Binary counter (20)
Multiplier
Default: Deka
Unit
Default: Dimensionless
Binary controlled step position information (BSC)
Table 3.4.8.6-1 Configurable BSC properties for OPC client
Property/ Parameter
Value or Value range/
Default
Basic
Common Data Class
BSC
Addresses
Control Index
-1 to 65535
Default: -1
Description
Variation for control
Description
Common data class according to IEC
61850.
Indication index.
Object number for counter.
Specifies the multiplier for current SI unit.
SI unit for measurement as described in
IEC61850
Description
Common data class according to IEC 61850.
Control index.
1MRS756566