2.16 TECHNICAL SPECIFICATIONS.
The MIGII system complies with the following standards, which include the standards required by Community Directive 89/
336 for the CE marking, in line with European standards. It also complies with the European directive requirements for low
voltage, and the environmental and operating requirements established in ANSI standards C37.90, IEC 255-5, IEC 255-6
and IEC 68.
STANDARD
2
ELECTROSTATIC COMPATIBILITY AND INSULATION
EN 55011 (1991) / EN 61000-6-4 (2001)
EN 61000-6-2 (2001)
EN 55011 (1991) / EN 61000-6-4 (2001)
ENV 50204 (1995)
IEC 61000-4-2 (1995) / EN 61000-6-2 (2001) Electrostatic Discharge Immunity Test
IEC 61000-4-3 (1995) / EN 61000-6-2 (2001)
/ ENV 50204 (1995)
IEC 61000-4-4 (1995)
IEC 61000-4-5 (1995) / EN 61000-6-2 (2001) Surge Immunity Test
IEC 61000-4-6 (1996) / EN 61000-6-2 (2001) Injected RF Signals Immunity Test
IEC 61000-4-11 (1994) / EN 61000-6-2
(2001)
IEC 60255-22-1 (1988)
IEC 61000-4-8 (1993) / IEC 61000-4-8
(1993)
IEC 61000-6-2 (2001)
IEC 60255-5 (1977)
IEC 60255-5 (1977)
IEC 60255-5 (1977)
CLIMATIC TESTS
IEC 60068-2-1 (1990) + A1(1992) +
A2(1994)
IEC 60068-2-2 (1974) + A1(1993) +
A2(1994)
MAKE AND CARRY
ANSI C37-90:1990
VIBRATION, SHOCK AND BUMPS
IEC 60255-21-1 (1998)
IEC 60255-21-2 (1998)
2-26
DESCRIPTION
Conducted and Radiated Emission
Radiated Emisión Measurement
Radiated Electromagnetic Fields with
Frequency Modulation
Radiated RF Fields Immunity Test
Electrical Fast Transient Immunity Test
Voltage Dips and Interruptions Immunity
Tetst
1 MHz Burst Disturbance Test
50 Hz Magnetic Fields Immunity Test
Frequency Magnetic Fields Immunity Test
Measurement of Insulation Resistance
Impulse Voltage Test
Dielectric Test
Test Ad
Test Bd
Make and Carry
Sinusoidal vibration / Vibration endurance
Test
Shock response / Shock strength / Bumps
Test
MIGII Digital Protection for Electrical Machines
2 PRODUCT DESCRIPTION
2.16.8 TYPE TESTS & CERTIFICATIONS
CLASS
In the paragraph relatin to electrostatic
discharges, radiated RF fields, electrical fast
transient, surge, injected RF signals and
voltage dips and interruption immunity test
Group 1, Class A
10 V/m, 900 MHz
Level 4 CM (8 kV). Level 3 AM (8 kV)
Level 3 (10 V/m), 80-1000 MHz.
Level 3 (±2 kV except for communications
terminals RS-485 and RS-232 where the
level was ±1 kV) with a perfomance criteria
A.
Level 3 (±2kV CM, ±1kV DM)
Level 3 (10 V/m), 0.15 – 80 MHz.
Duration and Voltage described in the
related report.
Level 3 (±2.5 kV in common mode and ± 1
kV in differential mode) in the I/O terminals
specified in paragraph 4.2 of the
corresponding report.
Level 5 (100 A/m for continuous applications
and 1000 A/m for transient applications) with
a performance criteria A.
In the paragraph relating to mains
Frequency Magnetic Fields Immunity Test.
In the paragraph relating to insulation
resistance for all groups defined in
paragraph 4 of the report.
In the paragraph relating to impulse voltage
test for ±5 kV applicatios in common mode
and ± 1 kV in differential mode (class III) for
all the groups defined in paragraph 4 of the
correspond report.
In the paragraph relating to dielectric test for
2 kV, 50 Hz applications for all the groups
defined in paragraph 4 of the correspond
report.
Cold
Dry Heat
Class I
Class I
GEK-113188A