Vega VEGAPULS 63 Operating Instructions Manual page 88

Radar sensor for continuous level measurement of liquids
Hide thumbs Also See for VEGAPULS 63:
Table of Contents

Advertisement

11 Supplement
Response:
Parameter
Assign Unit Number
Set number of Floats
Request:
Parameter
Set number of Floats
Response:
Parameter
Set number of Floats
If the number is set to 0, no level is returned
Set Baud Rate
Request:
Parameter
Set Baud Rate
Response:
Parameter
Set Baud Rate
Example: U01B9600E71
Change instrument on address 1 to baudrate 9600, parity even, 7 data bits, 1 stop bit
Set Receive to Transmit Delay
Request:
Parameter
Set Receive to Transmit
Delay
88
Length
6 characters ASCII
Length
5 characters ASCII
Length
6 characters ASCII
Length
8 (12) characters ASCII
Length
11 characters ASCII
Length
7 characters ASCII
Code/Data
UuuNOK
uu = new Address
Code/Data
UuuFn
Code/Data
UuuFOK
Code/Data
UuuBbbbb[b][pds]
Bbbbb[b] = 1200, 9600 (default)
pds = parity, data length, stop bit (optional)
parity: none = 81, even = 71 (default), odd = 71
Code/Data
Code/Data
UuuRmmm
mmm = milliseconds (50 up to 250), default = 127 ms
VEGAPULS 63 • Modbus and Levelmaster protocol