Vega VEGAPULS 63 Operating Instructions Manual page 75

Radar sensor for continuous level measurement of liquids
Hide thumbs Also See for VEGAPULS 63:
Table of Contents

Advertisement

Gas phase
Temperature
Air
20 °C/68 °F
200 °C/392 °F -0.01 %
400 °C/752 °F -0.02 %
Hydrogen
20 °C/68 °F
200 °C/392 °F -0.02 %
400 °C/752 °F -0.02 %
Steam (satu-
100 °C/212 °F 0.26 %
rated steam)
180 °C/356 °F 0.17 %
264 °C/507 °F 0.12 %
366 °C/691 °F 0.07 %
Characteristics and performance data
Measuring frequency
Measuring cycle time
Ʋ Standard electronics approx.
Ʋ Electronics with increased sensitivity
approx.
Step response time
3)
Beam angle
4)
Ʋ Clamp 2", 3"
Ʋ Clamp 3½", 4"
Ʋ Slotted nut DN 50
Ʋ Slotted nut DN 80
Ʋ Flange DN 50, ASME 2"
Ʋ Flange DN 80 ... DN 150,
ASME 3" ... 6"
Emitted HF power (depending on the parameter setting)
Ʋ Average spectral transmission power
density
Ʋ Max. spectral transmission power
density
Ʋ Max. power density at a distance of
1 m
Time span after a sudden measuring distance change by max. 0.5 m in liquid applications, max 2 m with bulk
3)
solids applications, until the output signal has taken for the first time 90 % of the final value (IEC 61298-2).
Outside the specified beam angle, the energy level of the radar signal is 50% (-3 dB) less.
4)
EIRP: Equivalent Isotropic Radiated Power.
5)
VEGAPULS 63 • Modbus and Levelmaster protocol
1 bar
10 bar
(14.5 psig)
(145 psig)
0 %
0.22 %
0.13 %
0.08 %
-0.01 %
0.10 %
0.05 %
0.03 %
-
2.1 %
1.44 %
1.01 %
K-band (26 GHz technology)
450 ms
700 ms
≤ 3 s
18°
10°
18°
10°
18°
10°
-14 dBm/MHz EIRP
+43 dBm/50 MHz EIRP
< 1 µW/cm²
Pressure
50 bar
100 bar
(725 psig)
(1450 psig)
1.2 %
2.4 %
0.74 %
1.5 %
0.52 %
1.1 %
0.61 %
1.2 %
0.37 %
0.76 %
0.25 %
0.53 %
-
-
-
-
9.2 %
-
5.7 %
13.2 %
5)
11 Supplement
200 bar
(2900 psig)
4.9 %
3 %
2.1 %
2.5 %
1.6 %
1,1 %
-
-
-
76 %
75