Additional settings -
Reset
Menu
Setup
VEGAPULS 63 • Modbus and Levelmaster protocol
6 Set up the sensor with the display and adjustment module
After a reset, certain parameter adjustments made by the user are
reset.
The following reset functions are available:
Delivery status: Restores the parameter settings at the time of ship-
ment from the factory, incl. order-specific settings. Any stored false
signal suppression or user-programmed linearisation curve, as well
as the measured value memory, are deleted.
Basic settings: Restores the parameter settings, incl. special param-
eters, to the default values of the respective instrument. Any stored
false signal suppression or user-programmed linearisation curve, as
well as the measured value memory, are deleted.
Setup: Restores the parameter settings made in the menu item
Setup to the default values of the respective instrument. False signal
suppression, user-programmed linearisation curve, measured value
memory and event memory remain untouched. The linearisation is set
to linear.
False signal suppression: Deletes a previously created false signal
suppression. The false signal suppression created at the factory
remains active.
Peak values, measured value: Resets the measured min. and max.
distances to the current measured value.
The following table shows the default values of the instrument. De-
pending on the instrument version, not all menu items are available or
some may be differently assigned:
Menu item
Measurement loop name
Medium
Application
Vessel form
Vessel height/Measur-
ing range
Min. adjustment
Max. adjustment
Damping
Current output mode
Current output, min./max.
Lock adjustment
Default value
Sensor
Liquid/Water
Bulk solids/Crushed stones, gravel
Storage tank
Silo
Vessel bottom, dished form
Vessel top, dished form
Recommended measuring range, see "Technical data"
in the supplement.
Recommended measuring range, see "Technical data"
in the supplement.
0,000 m(d)
0.0 s
4 ... 20 mA, < 3.6 mA
Min. current 3.8 mA, max. current 20.5 mA
Released
51