Mounting Instructions - Vega VEGAPULS 63 Operating Instructions Manual

Radar sensor for continuous level measurement of liquids
Hide thumbs Also See for VEGAPULS 63:
Table of Contents

Advertisement

4 Mounting
Sealing to the process
16
You have to remove these plugs before electrical connection.
NPT thread
In the case of instrument housings with self-sealing NPT threads, it is
not possible to have the cable entries screwed in at the factory. The
free openings for the cable glands are therefore covered with red dust
protection caps as transport protection. The dust protection caps do
not provide sufficient protection against moisture.
Prior to setup you have to replace these protective caps with ap-
proved cable glands or close the openings with suitable blind plugs.
4.2

Mounting instructions

The PTFE washer of the antenna encapsulation serves also as
process seal.
After a certain time under the effect of large temperature changes,
PTFE plated flanges tend to lose their pre-tensioning. To compensate
for this, disc springs must be used with the flange screws.
We recommended using elastic washers or detent-edged washers:
Screw size
Disc spring type Article no.
M16,
/
"
Detent edged ring
5
8
Gross VS KD
M20,
/
"
Detent edged ring
3
4
Gross VS KD
M24,
/
"
Retaining washer
7
8
Schnorr VS, S
Note:
The retaining elements are included with the versions for process
temperatures -196 ... +200 °C (-321 ... +392 °F).
To seal effectively, the following requirements must be fulfilled:
1. Make sure the number of flange screws corresponds to the num-
ber of flange holes
2. Use of disc springs as previously described
Fig. 3: Use of disc springs
1
Disc spring
2
Sealing surface
3. Tighten screws with the necessary torque (see chapter "Technical
data")
2.32880
2.32881
2.32882
1
2
VEGAPULS 63 • Modbus and Levelmaster protocol