Report Level (and Temperature)
Request:
Parameter
Report Level (and Temperature)
Response:
Parameter
Report Level (and
Temperature)
PV in inches will be repeated if "Set number of floats" is set to 2. Hence 2 measured values can be
transmitted. PV value is transmitted as first measured value, SV as seconed measured value.
Information:
If the temperature should be transmitted in the Levelmaster protocol, then TV must be set in the
sensor to temperature.
PV, SV and TV can be adjusted via the sensor DTM.
Report Unit Number
Request:
Parameter
Report Unit Number
Response:
Parameter
Report Level (and Temperature)
Assign Unit Number
Request:
Parameter
Assign Unit Number
VEGAPULS 63 • Modbus and Levelmaster protocol
Length
4 characters ASCII
Length
Code/Data
24 characters ASCII
UuuDlll.llFtttEeeeeWwwww
uu = Address
lll.ll = PV in inches
ttt = Temperature in Fahrenheit
eeee = Error number (0 no error, 1 level data not readable)
wwww = Warning number (0 no warning)
The max. value for the PV to be transmitted is 999.99 inches (cor-
responds to approx. 25.4 m).
Length
5 characters ASCII
Length
6 characters ASCII
Length
6 characters ASCII
11 Supplement
Code/Data
Uuu?
Code/Data
U**N?
Code/Data
UuuNnn
Code/Data
UuuNnn
87