Surge pipe extension
Instructions and require-
ments, surge pipe
VEGAPULS 63 • Modbus and Levelmaster protocol
ø 60,3 mm
(2.37")
1
Fig. 14: Welding connection with surge pipe extension for different example
diameters
1
Position of the welded joint with longitudinally welded pipes
Instructions of orientation of the polarisation:
•
Note marking of the polarisation on the sensor
•
With threaded versions, the marking is on the hexagon, with flange
versions between two flange holes
•
The marking must be in one plane with the holes in the surge pipe
Instructions for the measurement:
•
The 100 % point must be below the upper vent hole and the
antenna edge
•
The 0 % point is the end of the surge pipe
•
During parameter adjustment, select "Application standpipe" and
enter the tube diameter to compensate for errors due to running
time shift
•
A false signal suppression with the installed sensor is recom-
mended but not mandatory
•
The measurement through a ball valve with unrestricted channel
is possible
ø 88,9 mm
15 mm
(0.59")
2 mm
(0.08")
1
4 mm
(0.16")
4 Mounting
(3.5")
26 mm
(1.02")
2 mm
(0.08")
5 mm
(0.20")
23