9 Diagnosis, asset management and service
Fault description
6. Measured value re-
mains momentarily
unchanged during fill-
ing and then jumps to
the correct level
7. Measured value
jumps towards 0 %
during filling
8. Measured value
jumps towards 100 %
during filling
9. Measured value
jumps sporadically to
100 % during filling
10. Measured value
jumps to ≥ 100 % or
0 m distance
Measurement error during emptying
Fault description
11. Measured value re-
mains unchanged in
the close range during
emptying
68
Error pattern
Reason
Turbulence on the product
surface, quick filling
0
time
Amplitude of a multiple echo
(vessel top - product surface) is
larger than the level echo
0
time
The level echo cannot be distin-
guished from the false signal at
a false signal position (jumps to
multiple echo)
Due to strong turbulence and
foam generation during filling,
the amplitude of the level echo
sinks. Measured value jumps to
false signal
0
time
Varying condensation or con-
tamination on the antenna
0
time
Level echo is no longer
detected in the close range
due to foam generation or false
signals in the close range. The
0
sensor goes into overfill protec-
time
tion mode. The max. level (0 m
distance) as well as the status
message "Overfill protection"
are outputted.
Error pattern
Reason
False signal larger than the level
echo
Level echo too small
0
time
Rectification
Check parameters, change if
necessary, e.g. in dosing vessel,
reactor
Check parameter "Application",
especially vessel top, type of
medium, dished bottom, high
dielectric constant, and adapt if
necessary
In case of interferences due to
installations in the close range:
Change polarisation direction
Chose a more suitable installa-
tion position
Carry out a false signal suppres-
sion
Carry out a false signal suppres-
sion or increase false signal
suppression with condensation/
contamination in the close
range by editing
Check measuring site: Antenna
must protrude out of the socket
Remove contamination on the
antenna
Use a sensor with a more suit-
able antenna
Rectification
Eliminate false signal in the
close range. Check: Antenna
must protrude from the socket
Remove contamination on the
antenna
In case of interferences due to
installations in the close range:
Change polarisation direction
After eliminating the false sig-
nals, the false signal suppres-
sion must be deleted. Carry out
a new false signal suppression
VEGAPULS 63 • Modbus and Levelmaster protocol