Mounting socket
VEGAPULS 63 • Modbus and Levelmaster protocol
Fig. 8: Mounting of the radar sensor with inflowing medium
Flush mounting
The best way to mount the sensor, also with respect to cleanability,
is flush on a block flange (flange without socket piece) or through a
hygienic fitting.
Mounting on socket
If the reflective properties of the medium are good, you can mount
VEGAPULS 63 on a socket piece. You will find recommended values
for socket heights in the following illustration. The socket end should
be smooth and burr-free, if possible also rounded. Then carry out a
false signal suppression.
Fig. 9: Deviating socket dimensions
The below charts specify the max. socket length h depending on the
diameter d.
Socket diameter d
50 mm
80 mm
100 mm
d
Socket length h
≤ 100 mm
≤ 300 mm
≤ 400 mm
4 Mounting
19