Vega VEGAPULS 63 Operating Instructions Manual page 64

Radar sensor for continuous level measurement of liquids
Hide thumbs Also See for VEGAPULS 63:
Table of Contents

Advertisement

9 Diagnosis, asset management and service
Failure (failure)
Code
Reason
Text message
F013
no measured value
available
F017
Adjustment span
too small
F025
Error in the lineari-
zation table
F036
No operable soft-
ware
F040
Error in the elec-
tronics
F080
F105
Determine meas-
ured value
F113
Communication
error
F125
Impermissible elec-
tronics temperature
F260
Error in the cali-
bration
F261
Error in the config-
uration
F264
Installation/Setup
error
64
The following table shows the codes and text messages of the status
message "Failure" and provides information on causes as well as
corrective measures.
Sensor does not detect an echo
during operation
Antenna system dirty or defec-
tive
Adjustment not within specifica-
tion
Index markers are not continu-
ously rising, for example illogical
value pairs
Failed or interrupted software
update
Hardware defect
General software error
The instrument is still in the
start phase, the measured value
could not yet be determined
Error in the internal instrument
communication
Temperature of the electronics
in the non-specified range
Error in the calibration carried
out in the factory
Error in the EEPROM
Error during setup
False signal suppression faulty
Error when carrying out a reset
Adjustment not within the vessel
height/measuring range
Max. measuring range of the
instrument not sufficient
Rectification
Check or correct installation
and/or parameter settings
Clean or exchange process
component or antenna
Change adjustment according
to the limit values (differ-
ence between min. and max.
≥ 10 mm)
Check linearisation table
Delete table/Create new
Repeat software update
Check electronics version
Exchanging the electronics
Send instrument for repair
Exchanging the electronics
Send instrument for repair
Disconnect operating voltage
briefly
Wait for the end of the switch-on
phase
Duration up to approx. 3 min.
depending on the version and
parameter settings
Disconnect operating voltage
briefly
Send instrument for repair
Check ambient temperature
Insulate electronics
Use instrument with higher
temperature range
Exchanging the electronics
Send instrument for repair
Repeat setup
Repeat reset
Check or correct installation
and/or parameter settings
Use an instrument with bigger
measuring range
VEGAPULS 63 • Modbus and Levelmaster protocol
DevSpec
Diagnosis Bits
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 12
Bit 7
Bit 8
Bit 9
Bit 10