Technical Data - Siemens SINAMICS S120 Manual

Sinamics family modular motion control drives
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

DC Link Components
4.2 Chassis
Figure 4-13
4.2.2.4

Technical data

Table 4-9
What are the technical data of the braking resistors
Order No.:
P
power (rated power)
DB
P
power (peak power)
15
Max. current
Cable entry
Line connection
Max. connectable cable cross-section
Degree of protection
Width x height x depth
Thermoswitch (NC contact)
maximum contact load
connecting cable
Weight
140
Dimension drawing, 50 kW/250 kW resistor
Units
kW
kW
A
mm²
mm
kg
6SL3000–1BE31-3AA0
25
125
189
Via cable gland M50
Via stud M10
50
IP 20
740 x 605 x 485
240 V
/ 10 A
AC
50
Manual, (GH6), 07/2007 Edition, 6SL3097-2AL00-0BP2
6SL3000–1BE32-5AA0
50
250
378
Via cable gland M50
Via stud M10
70
IP 20
740 x 1325 x 485
240 V
/ 10 A
AC
120
AC Drive